^SynOhrMultiSenseKNX-Eng-13.odt, 2014-05-06                                               Page 36 of 49

Configuration 
of the Speech 
Recognizer

Range

The maximum range of the speech recognition is 7 m at normal speaker volume. The range is 
specified in SynOhrStudio via parameter slider „Sensitivity“ (see Picture 22). The larger the room 

size is set the more sensitive are the microphones. This is noticeable in accordance with the 
sound level monitoring. Increased range means under circumstances decreased quality of the 

speech   recognition,   e.g.   if   a   playing   radio   is   close   to   the   SynOhr   MultiSense   KNX   but   the 
speaker a few meters away.

Master Slave 

For larger living rooms we therefore recommend a master slave operation with multiple stations, 
each set only to a standard range of about 4 m. Via the KNX

TM

 Bus and an additonal required 

Enertex® EibPC the signals can be evaluated and the speech recognitions can be synchronized 
with each other.

Keyword

Operation

In „SynOhrStudio“ the independent application from ETS the SprachSchatz for the commands is 

put together respectively compiled. One command consists of maximum four words. Under one 
command is understandable e.g. WALL LAMP BRIGHTER. So that SynOhr MultiSense KNX 

does   not   recognize   a   command   during   a   conversation   and   falsely   enables   an   action,   the 
SynOhr®SynOhr MultiSense KNX must be placed in the active mode first. This is also done with 

the help of speech recognition using the „Keyword“. This keyword is intensively checked by the 
recognizer and must be spoken isolated (pause at the end). If the recognizer has realized the 

keyword, so it gives a visual feedback through yellow flashing the ring and audible feedback by 
playing a short ring tone. During the phase of blinking and after playing the feedback sound the 

actual command must be spoken within three seconds.

Selection of 

Keywords

The keywords are selected so that these have different properties for recognition and stability. 

The artificial word ENERTEX or the word COMMAND are from our experience as particularly 
suitable. Should children operate the SynOhr MultiSense KNX by speech recognition before 

voice break, so is probably SYNOHR the best choice.

Sensitivity

With this setting the maximum range for speech recognition is set. The maximum range depends 

mainly on the room acoustics, the place of installation (e.g. acoustic shadow behind a wall), the 
speaker volume and (but less) of the number of used words. Up to a range of 4 m should a  

suitable everyday use parameterization even under difficult circumstances. For the range it is 
important whether it is spoken frontally or from one side. Spoken laterally the signal is more than 

50 % degraded. Therefore the human being automatically turns the head towards the speaker.

Additionally the similarity of the selected words and the room acoustic plays a large role in 

theses distances. If the noise sources (radio etc.) are louder and closer to the SynOhr than the 
speaker a recognition is not possible. If two people have a conversation a third person cannot 

operate the SynOhr from the same distance. Also note the chapter in the manual for choosing a 
suitable location. In order to „listen“ acoustically larger areas, it definitely takes more than one 

slave.

The   following   table   specifies   the   operating   range   adjustment.   The   situation   with   a   lot   of 

resonances are often to be found in the corridor or rooms with lots of tiles and no wallpaper. 
Incorrect   parameter   here   means   that   very   probably   a   recognition   about   possibly   greater 

distances are possible, but this is not robust against interference noise.

Because in hallways or tiled rooms and without wallpapers echo and resonances are existing, 

you have to work with smaller „Room Size“ as in rooms with sound-absorbing elements (wooden 

Enertex

®

 Bayern GmbH – Ebermannstädter Straße 8 -  91301 Forchheim - [email protected]

Содержание MultiSense KNX

Страница 1: ...roval by Enertex Bayern GmbH Enertex is a registered trademark of Enertex Bayern GmbH Other product and company names mentioned herein can be names of trademark or registered trademarks of their respe...

Страница 2: ...ick Start 14 ETS 14 Load Vocabulary 14 Choose Keyword 15 Define Command Sequences 15 Create SD Data 16 License Key 16 Restart 16 Menu Structure on the Device 17 Operation 17 Menu Structure 17 KNX 19 E...

Страница 3: ...5 Similarities 45 Parameter Clarity 45 Parameter Room Size 45 Override 45 Range and Master Slave 46 Room Acoustics 46 Commands 46 Experts Settings 47 Basics 47 Noise Level 47 Feedback Time 47 Ready Si...

Страница 4: ...t of the product and must remain with the end user The device must not be used for applications with potential danger malfunction The measurement of the sound pressure is not suitable for monitoring h...

Страница 5: ...t the lateral edges a colored ambient lighting is installed The brightness of the lighting can be adjusted automatically via built in brightness sensor to the ambient light be adjusted or turned off T...

Страница 6: ...uct data base Planning installation and commissioning are carried out with the help of KNX certified software The built in speech is parameterized using the freely available program SynOhrStudio You w...

Страница 7: ...should be preferred instead of place 3 because at the door are presumed noises or speaking people The max range depends on room acoustics the place of installation e g acoustic shadow behind the wall...

Страница 8: ...to the visible side comp Picture 5 Picture 5 SD Card Placement There is a file key on the supplied card This file defines with which model variant see page 5 SynOhr MultiSense KNX is operated and migh...

Страница 9: ...rnally measured or externally measured temperature at external temperature additionally extern symbol Clock symbol for indicating a time Lux display o the brightness value in Lux kLux display of the b...

Страница 10: ...on adjustment value High symbol for usage the menus Speaker symbol will be turned on automatically while sound output playing a song Minus for the operation adjustment value Down symbol for usage the...

Страница 11: ...hts ambience ring display an automatic lighting control depending on the ambient lighting can be turned on Starting from the max illumination is specified via the ETS or the internal menu comp page 16...

Страница 12: ...specified by the user in steps from 0 to 100 This will be parameterized by the ETS or the internal menu comp page 16 It is possible to regulate the brightness of light on the sensor automatically The...

Страница 13: ...ate SD data 5 License key 6 Restart ETS Picture 8 ETS Parameterization In the ETS each speech command is assigned to an action and linked to the corresponding group address see page 39 Load Vocabulary...

Страница 14: ...11 Choose Keyword Define Command Sequences Using Drag and Drop command sequences can be set for each speech command see picture 12 Picture 12 Define Command Sequences The following applies No 1 ETS s...

Страница 15: ...supplied card This file defines with which model variant see page 5 SynOhr MultiSense KNX is operated and might not be deleted The data contained in the file represent a software key for the features...

Страница 16: ...c display shows each the level and the submenu in the form Mainmenu Submenu e g 1 02 The touch buttons work per step function with small dead time and key repeat The key repeat is switched off after a...

Страница 17: ...ch recognition after update of the SD card ON OFF 4 03 TRAINER Setting the language trainer respectively not on all versions Male Female 4 04 UP Exit menu Up one level 5 AUDIO 5 01 AMP Volume of outpu...

Страница 18: ...rated database PlugIn usable The required product database ist available in VD4 format For the ETS2 and older versions of ETS3 is no product database available ETS Application Overview Picture 14 Main...

Страница 19: ...from the values of the basic level Automatic or object oriented switch over between Heating and Cooling Setpoint shift temporarily or permanently possible by operating the function keys on the device...

Страница 20: ...reas 0 0 to 9 9 Lux and 10 to 9999 Lux Measurement of the sound level Premium Edition only in association with Enertex EibPC with setting a threshold The default values can be taken from the pictures...

Страница 21: ...nge in the basic setpoint temperature Enable disable speech recognition Display Picture 21 Configuration Display in the ETS Up to 5 display levels with variable presentation time on the numeric displa...

Страница 22: ...operation mode the set temperature is changed The calculated setpoint temperature of the regulator can queried with this object Licenses Starter Standard Premium ID Function Name Length Type Flags 2...

Страница 23: ...t on Heating 2 stage respectively Heating and Cooling 2 stage Licenses Starter Standard Premium ID Function Name Length Type Flags 9 Setpoint Add Coolingactor analog 8 bits u08 5 1 DPT_Scaling CT This...

Страница 24: ...objects Licenses Starter Standard Premium ID Function Name Length Type Flags 15 on off Building Protection Mode 1 bit b01 1 1 DPT_Switch WC This object can be switched over to the Building Protection...

Страница 25: ...ect Licenses Starter Standard Premium ID Function Name Length Type Flags 21 Measured Value Internal measured Humidity 16 bits f16 9 007 DPT_Value_Humidi ty R CT This objects contains the current humid...

Страница 26: ...set on Dimming or Blinds Licenses Starter Standard Premium The number of varies is depending on the license ID Function Name Length Type Flags 107 146 Speech Command Speech Command 8 bits 5 1 DPT_Sca...

Страница 27: ...ct switching telegrams can be sent when pressing the right touch button Depending on the configuration On Off or Shift telegrams are possible Note This object is only available if the parameter Button...

Страница 28: ...ol WCTU Via this object 4 bits telegrams can be sent when presseing the left touch button Depending on the configuration a percent value or a scene are possible Note This object is only available if t...

Страница 29: ...are possible Note The read value of the object is only defined if the object at least has been written once Licenses Starter Standard Premium ID Function Name Length Type Flags 163 on off Presence Det...

Страница 30: ...sent to the room controller to show it on the display See under parameter Display Numeric Display the value External Sensor Licenses Starter Standard Premium ID Function Name Length Type Flags 173 Au...

Страница 31: ...m 0 minimum brightness to 100 maximum brightness are possible Note The read value of the object is only defined if the object at least was written once Licenses Starter Standard Premium ID Function Na...

Страница 32: ...a communication object T Transmit Enables transferring of a value normally shows this flag the sending GA U Update Enables the updating of a communication object value at any feedback listen and synch...

Страница 33: ...re configured for word commands as command 1 to command 40 depending on the model variant The word commands are composed of the given vocabulary This vocabulary is provided by the Enertex Bayern GmbH...

Страница 34: ...23 Transmission of a Term through Drag Drop Depending on the license are up to 40 command sequences are assigned Please pay attention to the setting rules when creating the commands see page 43 Using...

Страница 35: ...nizer independent of the user via the KNXTM Parameterization of the ETS Setting the SynOhrStudio a vocabulary is required This includes the SprachSchatz for the language the necessary configuration da...

Страница 36: ...of Keywords The keywords are selected so that these have different properties for recognition and stability The artificial word ENERTEX or the word COMMAND are from our experience as particularly sui...

Страница 37: ...phrases distinctness of the words Setting Range less Echo Resonances Range more Echo Resonances 9 7 m Not usable 8 6 m Not usable 7 5 m Not usable 6 4 m 7 m 5 3 m 6 m 4 2 m 5 m 3 1 m 4 m 2 1 m 2 m 1...

Страница 38: ...0 All pronunciations of the keyword are accepted Here even remotely similar words can be recognized as keyword 1 Gradual increase of the necessary clarity of pronunciation 2 3 Default Value 4 From thi...

Страница 39: ...ds can be changed without relying on the ETS e g by the user himself Picture 26 Example of a Command Sequence Excerpt ETS Independent of the SynOhrStudio must assigned to each speech command an action...

Страница 40: ...dio can for command2 then e g SCENE WINTER GARDEN be defined Picture 29 Call Scene 2 Value Commands If the command DIMMER SEVENTY PERCENT assigned to a command with SynOhrStudio so this can now also s...

Страница 41: ...ERCENT 204 NINETY PERCENT 229 HUNDRED PERCENT 255 Not KNX compliant Extensions The following extensions are depending on the version of the loaded SprachSchatz part of their vocabulary However these a...

Страница 42: ...RO 0 ONE 1 TWO 2 THREE 3 FOUR 4 FIVE 5 SIX 6 SEVEN 7 EIGHT 8 NINE 9 TEN 10 ELEVEN 11 TWELVE 12 Fraction Extension Word Value on KNX BUS _FRACTION HALF 0 ONE THIRD 1 A QUARTER 2 ONE FIFTH 3 Heating Coo...

Страница 43: ...Note also the next setting rule 3 Use the switching function of the KNX part Example WINTER GARDEN SHADING This command is placed on a switching object with switching The window will ascend when it i...

Страница 44: ...often better It should be noted that then it will be more difficult for the user under circumstances to activate the recognition especially for longer distances or ambient noises Compared with vowels...

Страница 45: ...s on wrong words or is generally not robust Therefore please avoid a too large room size Commands The recognition of commands is processed differently than that of the keyword Here the recognizer choo...

Страница 46: ...command is set via the menu item Feedback Time Overall five levels are adjustable from time lag Paralyzed up to fast Fast The feedback time is the time of break which the user must wait after spoken...

Страница 47: ...noises softly spoken under circumstances the spoken command is incorrectly assigned e g SCENE THREE instead of SCENE TWO Failure Symptoms Symptom Solution Frequent false triggering of the keyword Set...

Страница 48: ...pl Ing FH T M hlfelder Objects of the KNXTM Communication revised Licenses at Objects of the KNXTM Communication completed 7 09 12 2013 Stefanie Meier Chapter Quick Start added 8 10 1 2014 Dr Ing M Sc...

Страница 49: ...SynOhrMultiSenseKNX Eng 13 odt 2014 05 06 Page 49 of 49 Revision of screenshots Enertex Bayern GmbH Ebermannst dter Stra e 8 91301 Forchheim mail enertex de...

Отзывы: