900-0258-01-00 Rev A
33
Specifications
Table 2 Specifications
EnergyCell
1000XLC
Cells Per Unit
24
Voltage Per Unit
48V
Optimal Operating Temperature
77°F
(25°C)
Maximum Operating Range
–40°F to 122°F
(–40°C to 50°C)
Operating Temperature Range
(Storage)
–4°F to 104°F
(–20° to 40° C)
Operating Temperature Range
(Discharging)
–4° to 122° F
(–20° to 50° C)
Operating Temperature Range
(Charging)
32° to 104° F
(0° to 40° C)
Absorb or Equalize
Charge Voltage
58 Vdc
Maximum Charge Current
200 Adc
Recommended Charge Current
168 Acd
Charging Temperature
Compensation Factor
±5 mV / °C / cell
Relative Humidity
0% to ~95%,
non-condensing
Terminal
M10 bolt
Terminal Torque
2
531 Lbf
ꞏ
in
(28.1-33.8 N
ꞏ
m; 287-344 Kgf
ꞏ
cm)
System Weight
~4574 lb
(~2075 kg)
System Dimension L x W x H
21
13
/
16
× 44
3
/
16
× 67
5
/
16
″
(55.5 × 112.5 × 171 cm)
Warranty
10 year standard warranty (refer to warranty statement for more details)
Table 3 2V Ampere Hour Capacity to 1.80 Volts Per Cell at 77°F (25°C)
Discharge
in
Hours:
1 2 3 4 8 10 20 24 48 100
EnergyCell 1000XLC
447 554 630 692 816 848 958 988 1118 1220
Содержание Outback Power EnergyCell 1000XLC
Страница 1: ...EnergyCell 1000XLC Owner s Manual...
Страница 10: ...Introduction 10 900 0258 01 00 Rev A This page intentionally left blank...
Страница 28: ...Operation 28 900 0258 01 00 Rev A NOTES...
Страница 32: ...Troubleshooting and Maintenance 32 900 0258 01 00 Rev A NOTES...
Страница 35: ...EnergyCell Batteries 900 0258 01 00 Rev A 35 This page intentionally left blank...
Страница 36: ...Masters of the Off Grid First Choice for the New Grid 17825 59th Avenue N E Suite B Arlington WA 98223 USA...