0120011-J0 Rev M
62
7�1�2 Individual Channel Alarms
LED State
Individual Converter Status
Action
Green
Normal
None
Blinking Green
Remote shutdown enabled on
individual channel/converter
Can be reset by toggling Startup / Shutdown button
through the CXCI+ controller.
Blinking Yellow
Recoverable:
• OCP/Overload
• Vout low
Ensure the load is within rated current.
Check that output is within the regulation range.
Non-recoverable:
• Converter input fuse fail
Potential component failure. Replace with new module.
Red
Recoverable:
• OVP
OVP will cause the output to restart every two seconds
until the fault is removed. If the fault persists for 60
seconds, the output will shutdown for 60 seconds and
attempt a restart every 60 seconds until the fault is
cleared.
Non-recoverable:
• Converter output fuse fail
Failed fuses are not field replaceable. Replace with new
module.
Blinking Red
Recoverable:
• GFI
If the fault persists for 60 seconds the output will
shutdown for 30 seconds and attempt to restart every
30 seconds until the fault is cleared.
7�1�3 Troubleshooting the Fan Tray Status LED
LED State
Module Status
Action
Shelf Size
Green
Normal
None
6", 19", 23"
Blinking Green
Ambient temperature <20
°
C
None
19", 23"
Yellow
Recoverable:
• Ambient temperature high
Resets automatically when ambient temperature
reduces to approximately 85°C or below.
19", 23"
Blinking Yellow
Recoverable:
• Input voltage out of range
(high/low)
Fan operation is disabled if input voltage is not
within the range of 40-60Vdc.
19", 23"
Non-recoverable:
• Fan voltage low
Possible component failure. Replace fan tray.
19", 23"
Red
Fan fail
Replace fan tray.
6", 19", 23"
Содержание alpha LPS36
Страница 1: ...LPS36 Line Power System Technical Guide 0120011 J0 Effective 07 2020...
Страница 2: ......
Страница 4: ......
Страница 85: ......