17
0120011-J0 Rev M
LEDs
Each controller has three LEDs located on the front panel. These are used to display the alarm status of the power
system, controller progress and status during startup, as well as file transfers.
Alarm Conditions
The controller illuminates the LED that corresponds to the system alarm status. Only one LED is illuminated at a time
during alarm conditions. The following show the corresponding alarm status for each LED color:
Green
:
OK, no alarms
Yellow
: Minor alarm, no major alarms
Red
:
Major alarm
Progress and Status Indication
The LEDs are also used in the following situations:
•
Base unit validation – all three LEDs are on at the same time.
•
File transfer – when recovering from invalid firmware application – the red LED is illuminated.
Reset
Refer to Section "Controller Reset" on page 53 for reset options.
Figure 5 — Cordex CXCI+ controller front panel
Ethernet port
Soft reset: push once
Reset IP address: hold
for 3 seconds
LCD screen (displays
Voltage or Current)
Display pushbutton toggle
switch for Voltage or Current
Hard reset: push once
System status LEDs
Locking screw
CXCI+ Controller
The controller brings advanced monitoring technology to the Cordex series of converters. A single controller man-
ages up to 9 converter modules. This compact system controller is equipped with the complete range of Cordex
software features, including the following:
•
Ethernet port for local and remote communications
•
User definable alarms
•
Daily logging of power system events and system statistics