27
0120011-J0 Rev M
The temperature below the LPS36 shelf shall not exceed 45°C. If the temperature exceeds 45°C, then the output
power is derated at 2.5W/°C as per the graph below.
45
°
C
65
°
C
0
10
20
30
40
50
60
70
80
90
100
110
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
LP
S3
6
Av
er
ag
e
Ou
tp
ut
p
er
C
han
ne
l (
W
)
Ambient Temperature (
°
C)
Output Power Derating Curve
Figure 13 — Output Power Derating Curve
LPS36 Average Output = Line loss (I
2
R) + Remote down-conv Remote equipment
load.
NOTE:
6�4�2 Forced Air Cooling with LPS Fan Tray
—
Two and Three Shelves
Two and three shelves require a fan tray and two baffles to meet the specified cooling requirements for both CO and
OSP applications. Install the fan tray directly below either two or three converter shelves and a baffle tray below the
fan tray as shown below in Figure 14. In addition, install a baffle tray above the converter shelves.
Up to nine converter shelves can be managed by a single controller, provided each three contiguous shelves has fan
cooling.
Baffle tray
Baffle tray
Fan tray
Converter
shelves
Figure 14 — Multi-shelf System Mounting