44
ENERGYWALL.COM
INSTALLATION, OPERATION & MAINTENANCE MANUAL 717.814.5365
U-ERV/U-HRV
There are (3) different combinations of fan positions that affect airflow performance as displayed
below.
For each fan curve, additional options such as filters, coils, duct pressure, etc. should be summed
together and added to the “External Static Pressure” to determine each system’s airflow capabilities.
For systems larger than 600, divide the desired CFM by 600 and round up to the nearest whole number
to determine the number of units in the system. Then divide the total number of units calculated by
the desired CFM.
This resultant CFM is what should be used when reading each fan curve.
FAN
FAN
POSITION 1
FAN
FAN
POSITION 2
FAN
FAN
POSITION 3
FAN
FAN
POSITION 4
PERFORMANCE
AIRFLOW