28
ENERGYWALL.COM
INSTALLATION, OPERATION & MAINTENANCE MANUAL 717.814.5365
U-ERV/U-HRV
ALARM FAN MODE
The alarm fan mode can be set to either shut the unit down, shut the supply
fan down, or shut both fans down.
ALARM FAN SPEED
The alarm fan speed determines the speed at which the supply and/or exhaust
fan will run when the system is in an alarm state.
FAN START DELAY TIMER
The fan start delay timer will delay the fans from starting by a defined period after
the system has been enabled.
FAN STOP DELAY TIMER
The fan stop delay timer will delay the fans from shutting down by a defined period
after the system has been disabled.
COIL CONFIG
All settings related to coil configuration are currently being developed and will be
released in the next version of software.
ENABLED OPTIONS (PW: 56789)
The enable options menu is a password protected menu that allows the user to enable,
disable, or select the type of various control features. Once a feature is enabled, various
settings and setpoints can be set to tune the feature’s operation.
SCHEDULED OPERATION
Enables or disables scheduled operation of the system.
ECONOMIZER DAMPER
Allows the user to select temperature, enthalpy, or no economizer operation.
DEFROST
Allows the user to select modulating bypass damper, modulating supply fan, or no
defrost operation.
OPERATION
MENU DESCRIPTIONS