U-ERV/U-HRV
SHUT-OFF DAMPER
Enables or disables an onboard relay to control an auxiliary shut off damper. When
enabled, the fan start delay timer will be set to a minimum of 45 seconds and the
onboard relay will close when the system receives an enable command.
AUXILIARY HEAT
Enables or disables an onboard relay to control an auxiliary heater. When enabled,
the system will utilize an auxiliary heat 10k thermistor to determine when to activate
the auxiliary heat relay. The auxiliary heat relay can only close when the system is
enabled, and the supply fan is running.
FREEZESTAT
Enables or disables the freezestat feature.
COIL MODE
The coil mode configuration is currently being developed and will be released in the
next version of software.
FILTER ALARM MODE
The filter alarm mode is currently being developed and will be released in the next
version of software.
TEMP/RH SENSORS
Enables or disables temperature and relative humidity (RH) sensors within all four
quadrants of the system. Temp/RH sensors can be utilized with a BMS, economizer,
defrost, freezestat, and other optional features.
SERVICE INTERFACE
The service interface can be used to troubleshoot, diagnose, and test various features of
software by resetting faults and having read/write capability for all inputs and outputs.
ENSURE ADEQUATE AIRFLOW IN DESIRED AIRSTREAM IF TESTING ANY
HEAT/COOL FUNCTIONALITY.
OPERATION
MENU DESCRIPTIONS