INSTALLATION, OPERATION & MAINTENANCE MANUAL 717.814.5365
27
ENERGY WALL
TM
U-ERV/U-HRV
MANUAL PURGE CONFIG
When the manual purge feature is enabled via the home screen, the fans and/or bypass
damper will adjust based on configured settings for a defined period. Once the timer expires,
the system will continue standard operation. If the manual purge feature is disabled at any
time within the defined period, the system will return to standard operation.
PURGE MODE
A purge selection on the home screen will force the supply fan and/or exhaust fan to
the desired setpoint for a defined time as set in the purge fan speed and purge timer
menus.
PURGE DAMPER POSITION
The purge damper position sets the damper to run in full core bypass or no core
bypass when manual purge mode is enabled.
PURGE TIMER
The purge timer determines how long the manual purge feature runs for before
expiring.
PURGE FAN SPEED
The purge fan speed determines at what speed the supply and exhaust fan operate at
when the manual purge feature is enabled.
ALARM INPUT CONFIG
When an alarm input signal is received, the system will enter an alarm state. "Alarm Fan
Mode" can be configured in one of the following modes:
Unit Shutdown
- supply and
exhaust fans off,
Supply
- supply fan speed set to "Alarm Fan Speed'',
Exhaust
- exhaust
fan speed set to "Alarm Fan Speed",
Both
- Supply and Exhaust speeds set to "Alarm Fan
Speed. "Alarm Fan Speed" can be set between 0-100% fan speed.
OPERATION
MENU DESCRIPTIONS