U-ERV/U-HRV
Holding Registers Continued (read/write numerical values)
Name
Modbus
Address
BACnet
ID
Format
Description
Occupied Exhaust Fan Min Speed
40065
69
Occupied Exhaust Fan Max Speed
40066
70
Unoccupied Supply Fan Min Speed
40067
71
Unoccupied Supply Fan Max Speed
40068
72
Unoccupied Exhaust Fan Min Speed
40069
73
Unoccupied Exhaust Fan Max Speed
40070
74
CO
2
PPM Setpoint
40071 - 40072
75
32 bit
unsigned
integer
Parts Per Million
CO
2
Occupied PPM Setpoint
40073 - 40074
76
CO
2
Unoccupied PPM Setpoint
40075 - 40076
77
Pressure Differential Setpoint
40077 - 40078
78
32 bit
floating
point
Pascals
Pressure Differential Occupied
Setpoint
40079 - 40080
79
Pressure Differential Unoccupied
Setpoint
40081 - 40082
80
Quadrant A Airstream
40083
160
16 bit
integer
0: Outside Air
1: Supply Air
2: Return Air
3: Exhaust Air
System Size
40084
161
0: 600 CFM 5:3600 CFM
1: 1200 CFM 6:4200 CFM
2: 1800 CFM 7:4800 CFM
3: 2400 CFM 8:5400 CFM
4: 3000 CFM 9:6000 CFM
Damper Offsets
40085 - 40104
150 -
159
32 bit
signed
integer
-180 to 180 degrees, each of ten
dampers has two modbus
registers.
Fan Control Mode
40105
169
16
bit
integer
0: Manual 3: CO
2
1: Analog 4: Pressure
2: BMS
Schedule Times
40106 - 40161
170 - 225
See Schedule Section
OPERATION
BACNET/MODBUS POINTS