FAN CONTROL SETPOINTS
All fan speed control set points, minimums, and maximums for the supply and
exhaust air streams in any fan mode can be found within this menu. If scheduling is
enabled, an occupied and unoccupied set point can be set for each airstream. More
details on fan mode functionality can be found under the menu “FAN MODE.”
ECONOMIZER SETPOINTS
All setpoints to control the enthalpy or temperature only economizer can be found
within this menu.
ECONOMIZER TEMP BAND
When in economizer temperature mode, the economizer temp band is used to
determine the damper bypass percentage by relating it to the economizer
activation temperature, the return temperature, and the outdoor air
temperature.
ECONOMIZER ENTHALPY BAND
When in economizer enthalpy mode, the economizer enthalpy band is used
to determine the damper bypass percentage by relating it to the economizer
activation enthalpy, the return enthalpy, and the outdoor air enthalpy.
ECONOMIZER DISABLE TEMP
The economizer disable temp will restrict the economizer from activating and
also shut the economizer off while active when the outdoor air temperature
drops below the economizer disable temp. Used in both enthalpy and
temperature economizer modes.
ECONOMIZER ACTIVATION TEMP
The economizer activation temp will enable the economizer when the outdoor
air temperature drops below the economizer activation temp. Used in both
enthalpy and temperature economizer modes.
ECONOMIZER ACTIVATION ENTHALPY
The economizer activation enthalpy will enable the economizer when the
outdoor air enthalpy drops below the economizer activation enthalpy. Used
in enthalpy economizer mode only.
DEFROST SETPOINTS
All setpoints to control the defrost operation can be found within this menu.
DEFROST SUPPLY TEMP
The defrost supply temp is used to set the damper bypass percentage or fan
speed so the supply air never drops below setpoint.
OPERATION
MENU DESCRIPTIONS