Status at: January 2013
39
4.
The circuit breaker must be returned to Pos. 1 after the
test has been completed and the generator must be re-
started so that it can be used again.
1.
Plug in the device and switch on.
The displayed symbol
(see Figure 4-5-(8))
and the position
of the circuit breaker indicate the result:
Symbol
Significance
lights up red
Insulation
fault (≤ 23 kΩ)
Yellow
Insulation fault (≤ 34.5 kΩ)
stays off
Connected unit is OK
Table 4.5: Insulation monitoring whilst running without switching off
If an insulation fault exists and the unit was previously
OK when tested without a device connected (see above),
the insulation fault has been caused by the device.
2.
After the device has been switched off and unplugged,
the circuit breaker must be returned to Pos. 1, and the
generator must be restarted, in order for the device to be
operated again.
Insulation monitoring
whilst running: