WARNING!
Electric shocks cause injury or death.
Do not earth the generator.
Do not connect protective conductor to an existing po-
tential equalisation line.
Do not connect the generator to an existing electrical
grid.
Fig. 4-4: Check the protective conductor
1.
Insert test cable into socket
(
Fehler! Verweisquelle konnte
nicht gefunden werden.
-(2))
.
2.
Hold a test tip an a metallic, blank location on the device.
The test lamp
(
Fehler! Verweisquelle konnte nicht gefunden
werden.
-(1))
on the multifunction display shows the result:
Test lamp
Significance
lights up green
protective conductor is OK
stays off
Protective conductor defective / not present
Table 4.1: Protective conductor test lamp
The protective conductor / potential equalization for this
device has been checked.
Check the protective
conductor
Proceed as follows to
check the protective
conductor between the
consumer and the
generator: