42
Version: January 2013
Figure 4-7: FI protection switch
1.
The generator must be started.
2.
Put the protection switch
(seeFigure 4-7-(20))
into position 1.
3.
Activate the test switch
(seeFigure 4-7-(10))
.
The switch position displays the result
(seeFigure 4-7-(20))
:
Symbol
Significance
Position I
Switch does not trigger. FI protection switch is defective.
Position 0
Switch triggers. FI protection switch is working properly.
Table 4.6: FI protection switch test
The device has been tested in compliance with DIN VDE
0100-551.
Checking the FI protection