Special fittings / using accessories
Insulation monitoring without E-MCS 3.0
Version: May 2011
ESE 808 / 1308 / 1408 DBG ES DU PLEX SILENT
53
1. Plug in the consumer and switch on.
The lamp
(see Fig. 5-4-(1))
and the position of the circuit
breaker indicates the result:
Lamp
Result
Meaning
Red
Circuit breaker jumps to Pos. '0’
Insulation fault (
≤
23 k
Ω
)
Red
Circuit breaker stays in Pos. ‘1’
Insulation fault (
≤
34.5k
Ω
)
Stays off
Circuit breaker stays in Pos. ‘0’
Connected unit is OK
Table 5.9: Insulation monitoring whilst running without switching off
If an insulation fault exists and the unit was previously
OK when tested without a consumer connected up to it
(see above), then the insulation fault has been caused by
the consumer.
2. The reset button must be pressed after switching off and
disconnecting the consumer
(see Fig. 5-4-(2))
and the circuit
breaker must be turned to Pos. 1 so that the unit can be
used again.
Insulation monitoring
whilst running:
Содержание ESE 1308 DBG ES DUPLEX SILENT
Страница 7: ...Table of Contents Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 7...
Страница 11: ...General information Safety symbols Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 11 Notes...
Страница 16: ...General Safety Regulations Intended use Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 16...
Страница 42: ...Operation Putting the generator out of service Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 42 Notes...
Страница 75: ...Troubleshooting Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 75 Notes...
Страница 79: ...Replacement parts Sound absorbing hood Version May 2011 ESE 808 1308 1408 DBG ES DUPLEX SILENT 79 Notes...