Engineering
WirelessHART Fieldgate SWG70
90
E Hauser
10.5
EtherNet/IP configuration
Note!
• The "EtherNet/IP" function is only available on WirelessHART Fieldgate models with the
version "SWG70-xx-3". See Chapter 2.3 "Ordering information" on page 11.
The Fieldgate SWG70-xx-3 makes cyclic data available from up to 39 devices
(WirelessHART Adapters and field devices) via EtherNet/IP. In addition, data from Fieldgate
itself can also be made available via EtherNet/IP. Fieldgate offers 10 cyclic data exchange
connections for this purpose. Cyclic data from up to 4 devices can be exchanged via a data
exchange connection.
10.5.1 Setting up an EtherNet/IP connection
1. Set up the WirelessHART network. See Chapter 5.3 "Connecting to Ethernet" on
page 24. See Chapter 7.1 "Ethernet connection" on page 34.
2. Define the HART descriptors for all the HART and WirelessHART field devices that
should be monitored via EtherNet/IP according to the naming conventions. See
Chapter 10.5.2 "Assigning data exchange connections via HART descriptors" on
3. Define the burst commands for all the HART and WirelessHART field devices that
should be monitored via the cyclic EtherNet/IP connection. See Chapter 10.5.3 "Burst
commands for cyclic data exchange" on page 91.
4. Integrate the WirelessHART Fieldgate SWG70 into your control system. For this
purpose, install the Add-On Profile (AOP) or the EDS file. See Chapter 10.5.4
"Integrating SWG70 into a PLC via EtherNet/IP" on page 92.
5. Make the configuration for cyclic or direct data exchange with the HART and
WirelessHART field devices. See Chapter 10.5.5 "Cyclic data exchange via the
ControlLogix® controller system" on page 92.
10.5.2 Assigning data exchange connections via HART descriptors
The "HART Descriptor" parameter is used to make available the cyclic data from field devices
and Fieldgates. You can configure this parameter in the corresponding DTM or DD.
The "HART Descriptor" parameter has the following structure for all field devices and for the
Fieldgates:
• Up to 13 characters of customized text
• Identifier with 3 characters.
The customized text is used to identify the devices in readable format. You can enter the tag
name here for example.
The identifier is used to assign the cyclic data and has the following structure:
• 1st character: @
• 2nd character: choice of one of the 10 cyclic data exchange connections. The letter "A"
corresponds to connection "1" and the letter "J" to connection "10".
• 3rd character: device identifier
The identifier @A0 is pre-assigned by Fieldgate and may not be used for WirelessHART
Adapters or field devices.