Modbus Interface
WirelessHART Fieldgate SWG70
120
E Hauser
16.2.2 Digital input/output devices
There is no automatic mapping of the Input Status registers. the user must generate the
mapping table either semi-automatically or manually.
• A semi-automatic mapping will duplicate the values entered under the "Generate" tab for
all devices in the network, irrespective of device type
• A manual mapping allows the table to be built up for each individual device
(recommended)
Discrete devices publish their values by "bursting" HART CMD 64386. This tells Fieldgate
SWG70 how many discrete values a device has as well as the index of the first discrete value.
A maximum of 256 discrete values can be mapped for each device. At the moment, Fieldgate
SWG70 does not map the status of the device.
Each discrete value is published as a UNIT16. Fieldgate SWG70 first splits the data into two
bytes then reserves 8 registers for each byte, i.e. one for each bit.
• The
Least Significant Byte
(x) maps Bits 0 - 7 of the value with Index x
• The
Most Significant Byte
(x) maps Bits 8 - 15 of the value with Index x
Index "x" is not determined by the position of the discrete value in the device burst list but
rather by its position in CMD 64385. For example, if the 1st and 4th discrete variables are
selected in the burst list, the corresponding indexes are "0" and "3". Assuming that all bytes
are of interest, the user must enter the following lines:
• Tag Device 1: Least Significant Byte0
Tag Device 1: Most Significant Byte 0
Tag Device 1: Least Significant Byte 3
Tag Device 1: Lost Significant Byte 3
The following (manual) mapping table results:
When Fieldgate SWG70 receives CMD 64.386, it checks whether the variables have been
mapped, then enters the associated information. Any values that are not mapped are
discarded.
Reference address
Device
Discrete Variable
Bit
Byte (Variable Index)
100001
Device 1
Variable 1
Bit 0
LSB (0)
100002
Device 1
Variable 1
Bit 1
LSB (0)
...
100007
Device 1
Variable 1
Bit 6
LSB (0)
100008
Device 1
Variable 1
Bit 7
LSB (0)
100009
Device 1
Variable 1
Bit 8
MSB (0)
100010
Device 1
Variable 1
Bit 9
MSB (0)
...
100015
Device 1
Variable 1
Bit 14
MSB (0)
100016
Device 1
Variable 1
Bit 15
MSB (0)
100017
Device 1
Variable 4
Bit 0
LSB (3)
...
100025
Device 1
Variable 4
Bit 7
LSB (3)
100026
Device 1
Variable 4
Bit 8
MSB (3)
...
100032
Device 1
Variable 4
Bit 15
MSB (3)
...