Engineering
WirelessHART Fieldgate SWG70
76
E Hauser
Input Register parameters
Parameter
Meaning
Example
Default
Table
Registers
Defines the start register for the HART device value
– For Input Register the first value is normally 1
– The initial value can be overwritten only after a device has
been selected in the Long Tag drop-down menu
– Subsequent start registers are automatically generated
13
1
End Register
End register for Digital I/O device values (generated
automatically)
14
65536
Long Tag
Click to open a drop-down list of connected network devices
–
–
IO-Card
Identifier of fieldgate card used by the device
–
–
Channel
Identifier of card channel used by the device
–
–
Value
Click to open a drop-down list of values for the selected device –
–
Delete button
Enter an appropriate value into the field
– which opens when a value is selected
Generate
Start Register
Defines the start register for the HART device value
– For Input Registers this is normally 1, depending on the
Modbus system in use
13
1
Generation Order
Order in which the devices are mapped to the Modbus
registers.
• Index: According to the index number, see Instrument List,
for example. See Chapter 10.1 "Instrument List" on page 64.
• Alphabetical: In alphabetical order according to the Long
Tag
• Alphabetical (sub-device): In alphabetical order according to
the Long Tag of the sub-device.
• IO card & channel: According to the IO card & channel
number of the wireless device.
• IO card & channel (sub-device): According to the IO card &
channel number of the sub-device.
–
–
Value
Click to open a drop-down list of values for the selected device –
–
Value field
Enter an appropriate value into the field
– which opens when a value is selected
0
0
Delete button
Depending upon position, deletes the table or the table line
–
–
Default Settings
Adds all HART Command 3 values to the value list, see See
Chapter 16 "Modbus Interface" on page 114.
–
–
Generate
Writes mapping table to table in Table tab
–
–
Delete all mappings
• Checked: Overwrites any table already in Table tab
• Unchecked: Adds any new devices found to existing table.
–
–
Operating elements
Import
Imports a mapping table in CSV format
–
–
Export
Exports the current mapping table in CSV format
–
–
Refresh
Loads the mapping table currently stored in Fieldgate SWG70 –
–
Apply
Stores the current mapping table to Fieldgate SWG70
–
–
Содержание WirelessHART Fieldgate SWG70
Страница 2: ......
Страница 134: ...WirelessHART Fieldgate SWG70 134 Endress Hauser ...
Страница 137: ...WirelessHART Fieldgate SWG70 Endress Hauser 137 ...
Страница 138: ...www addresses endress com www addresses endress com ...