Commissioning
WirelessHART Fieldgate SWG70
34
E Hauser
7.1
Ethernet connection
The Ethernet connection of Fieldgate SWG70 allows communication with a computer via the
integral Web Server or via FieldCare.
The following requirements must be met:
• Internet Protocol TCP/IP is installed on your computer and is active.
• You have administration rights for your computer and network.
• You have an set of IP addresses that have been authorized by your IT department.
• Any proxy server for your Internet Browser is disabled.
• Firewalls allow communication on port 80, 433, 502, 3333 and 5094.
Fieldgate SWG70 is delivered with the default IP address:
• 192.168.1.1
NOTICE!
• By default, the IP address of the WirelessHART Fieldgate EtherNet/IP version is
automatically assigned via DHCP. Please contact your network administrator to identify
the automatic set IP address, if necessary.
• Alternative 3
rd
party IP scanner software i.e. “BOOTP Utility Software” from Rockwell
Automation enables you to scan the Ethernet network and being able to assign a dedicated
IP address i.e. 192.168.1.1 to the WirelessHART Fieldgate. Please consider WirelessHART
Fieldgate MAC address is required to be able to set a dedicated IP address with “BOOTP
Utility Software” from Rockwell Automation.
• Please find below path to Rockwell Automation “BOOTP Utility Software” download and
instruction page:
1. Go to http://www.rockwellautomation.com
2. Click “Products”
3. Click “Reliance Electric Drives”
4. Click “Software”