Tankvision Gauge Link
Operation
Hauser
29
Once the above has been done type in
DEVICES(return)
to confirm your configuration is
correct.
Example 3
A system requires to be connected to 6 of NRF590 gauges (emulating Enraf GPU) with
address 01 – 06.
Level and temperature are required from all gauges.
Host baud rate is 9600, with a parity of none. BPM baud rate is 1200.
0=1(return)
Level address = 1 (modbus address = 1)
100=1(return)
Temp address = 1
1=2(return)
Level address = 2 (modbus address = 2)
101=2(return)
Temp address = 2
2=7(return)
Level address = 7 (modbus address = 7)
102=7(return)
Temp address = 7
302=7(return)
Water register 07 from address 7
902=38(return)
Product pressure register 38 from address 7
3=8(return)
Level address = 8 (modbus address = 8)
103=108(return)
Temp address = 108
4=21(return)
Level address = 21 (modbus address = 21)
104=21(return)
Temp address = 21
(return)
Enter
Result
FTS=1200(return)
HTS=9600(return)
HPA=N(return)
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
100=1(return)
Temp address = 1
1100=78(return)
Gauge type is a NRF590 (78)
1=2(return)
Level address = 2 (modbus address = 2)
101=2(return)
Temp address = 2
1101=78(return)
Gauge type is a NRF590 (78)
2=3(return)
Level address = 3 (modbus address = 3)
102=3(return)
Temp address = 3
1102=78(return)
Gauge type is a NRF590 (78)
Enter