Operation
Tankvision Gauge Link
28
Hauser
Once the above has been done type in
DEVICES(return)
to confirm your configuration is
correct.
Example 2
A system requires to be connected to 5 off Emerson gauges. The modbus interface is 19200,
None, 8, 1.
• Gauge address = 1, needs level and temp.
• Gauge address = 2, needs level and temp.
• Gauge address = 7, needs level, temp, temp elements, live water from gauge register
analogue input current 2 and product pressure from gauge register HART input 2.
• Gauge address = 8, needs level. Temp and its elements is from a DAU with address 108.
• Gauge address = 21, needs level and temp. Gauge type is an TRL emulation coming from
a none Emerson gauge.
Ensure the Tankvision Gauge Link is the TRL/2 version.
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
100=1(return)
Temp address = 1
1100=83(return)
Gauge type is a servo (83)
1=2(return)
Level address = 2 (modbus address = 2)
101=2(return)
Temp address = 2
1101=82(return)
Gauge type is a radar (82)
2=5(return)
Level address = 5 (modbus address = 5)
102=5(return)
Temp address = 5
202=5(return)
Element temp address = 5
402=5(return)
Water dip address = 5
502=5(return)
Density = 5
1102=83(return)
Gauge type is a servo (83)
3=9(return)
Level address = 9 (modbus address = 9)
103=19(return)
Temp address = 19
203=19(return)
Temp address = 19
1103=82(return)
Gauge type is a servo (82)
4=20(return)
Level address = 20 (modbus address = 20)
104=20(return)
Temp address = 20
1104=78(return)
Gauge type is basic (78)
(return)
Enter
Result
HTS=1920(return)
HPA=N(return)
CONFIG(return)
Enable configuration
Enter
Result