Tankvision Gauge Link
Operation
Hauser
27
The below inputs to the Emerson REX gauge are mapped to the TRL/2 registers. These will
only be picked up from the gauge with the address in holding registers 0 -31. These will not
be picked up from a DAU.
For example:
A system has a REX gauge with an address of 2 and a DAU for temperature of 102. Live
water and vapour temperature is also required, these will be mapped to Analogue input
current 1 and HART input 1 respectively in the REX gauge. Configure the Tankvision Gauge
Link as follows:
7.1.9
Worked examples
Example 1
A system requires to be connected to 5 off Honeywell Enraf gauges. GPU baud rate is 1200.
The modbus interface is 9600, None, 8, 1.
• Gauge address = 1, needs level and temp. Gauge type 854.
• Gauge address = 2, needs level and temp. Gauge type 873.
• Gauge address = 5, needs level, temp, temp elements, water dip and density. Gauge type
854.
• Gauge address = 9, needs level. Temp and its elements are from an 864 with address 19.
Gauge type 873.
• Gauge address = 20, needs level and temp. Gauge type is an Enraf emulation coming from
a none Enraf gauge.
Ensure the Tankvision Gauge Link is the Enraf version.
Emerson REX input
TRL/2 Register
Analogue input current 1
06
Analogue input current 2
07
Analogue input current 3
08
Analogue input 1
30
Analogue input 2
32
HART Input 3
36
HART Input 2
38
HART Input 1
40
Enter
Result
CONFIG(return)
Enable configuration
0=2(return)
Level address = 2
100=102(return)
Temp address = 102
300=06(return)
Water from register 06 with address 2
700=40(return)
Vapour temp from register 40 with address 2
(return)
Enter
Result
FTS=1200(return)
Enable
HTS=9600(return)
Enable
HPA=N(return)
Enable