background image

Tankvision Gauge Link

Operation

Hauser

21

The numbers 78, 82 and 83 in Modbus holding register 1100 – 1131 represent:

78 = decimal value for ascii ‘N’ (Where N = NRF590)

82 = decimal value for ascii ‘R’ (Where N = RADAR)

83 = decimal value for ascii ‘S’ (Where N = SERVO)

When setting a value of 82 in holding registers 1100 – 1131 causes the Tankvision Gauge 

Link to poll for the ZQR command, which is the radar status register. 

When setting a value of 83 in holding registers 1100 – 1131 causes the Tankvision Gauge 

Link to poll for the ZQS command, which is the servo status register. 

When setting a value of 78 in holding registers 1100 – 1131 causes the Tankvision Gauge 

Link to not poll for any status registers and it will pick its status value from the ‘B’ record.

If holding registers 1100 – 1131 are set to anything other than 78, 82 and 83 then the 

status of the gauge will be picked up from the ‘B’ record and ZQR and ZQS will NOT be polled 

for.

DEVICES(return)

The devices and configuration parameters for the gauges which have been configured can be 

viewed at any time. This command allows you to look at the Modbus holding registers.

The data displayed lists the Modbus holding registers in columns of 100 registers. The first 

block to the left lists all the level addresses configured, the second block lists the temperature 

addresses configured, these blocks are the blocks of registers detailed in the Tankvision 

Gauge Link Modbus Map document. It can be seen at the top of each column shows which 

block of 100 registers is detailed. Down the left side the block register is incremented.

The example print out shows the configuration done in the above example:

As it can be seen the registers configured in the above example marry up with the data 

shown above.

The first, left most block of registers, shows the values of 001 and 015. These are the level 

addresses. The second block (0100) show the values of 001 (+00) and 015 (+01) these are 

the temperature addresses. This pattern is repeated up to block 1100, where it can be seen 

block 1100 (+00) contains the value 82 and block 1100 (+01) contains the value 83.

All the unused registers contain the value 255, which represents values which are out of 

range.

When connecting to Enraf gauges holding registers 600 – 631 are reserved and not used.

When connecting to SAAB Rosemount gauges holding registers 200 – 231, 400 – 431, 500 

– 531, 600 – 631 and 1100 – 1131 are not used.

All holding registers above 31 to the next 100 in the block are un-used.

The diagram below shows in more detail what each column and row represents.

The below is configures to poll for 3 gauges.

DEVICES

0000

0100

0200

0300

0400

0500

0600

0700

0800

0900

1000

1100

+ 00

001

001

001

001

255

255

255

255

255

255

255

082

+ 01

015

015

015

255

255

255

255

255

255

255

255

083

1

st

 gauge

Gauge address 01, Modbus address 01. Radar (82)

Level

(Reg 0000)

Temperature

(Reg 0100)

Temp elements

(Reg 0200)

Live water

(Reg 0300)

Содержание Tankvision Gauge Link NXA20

Страница 1: ...Products Solutions Services BA01335G 00 EN 01 14 71260205 Valid as of software version 1 1 0 Operating Instructions Tankvision Gauge Link NXA20 Installation Operation and Maintenance Manual...

Страница 2: ...eplate 7 3 3 Order code and device version 8 3 4 Registered trademarks 8 4 Technical specification 9 4 1 Environmental conditions 9 4 2 Electrical ratings 9 5 Installation 10 5 1 Mechanical installati...

Страница 3: ...on Failure to avoid this situation will result in serious or fatal injury A0011190 EN WARNING This symbol alerts you to a dangerous situation Failure to avoid this situation can result in serious or f...

Страница 4: ...n A0011195 Reference to page Refers to the corresponding page number Series of steps A0018373 Result of a sequence of actions Symbol Meaning 1 2 3 Item numbers Series of steps A B C Views A0011187 Haz...

Страница 5: ...nal protection for the device and device data transfer must be implemented by the operators themselves 2 3 Designated use 2 3 1 Application The Tankvision Gauge Link is a tank gauging protocol convert...

Страница 6: ...mpetent personnel who are aware of and fully understand the instructions provided herein Conversions to the device Unauthorized modifications to the device are not permitted and can lead to unforeseea...

Страница 7: ...ce Viewer www endress com deviceviewer 3 2 Nameplate nameplate_NXA20 1 Address of manufacturer 2 Device name 3 Order code 4 Extended order code Ext ord cd 5 Serial number Ser no 6 Data Matrix Code 7 D...

Страница 8: ...red trademarks Microsoft Windows and Internet Explorer Registered trademarks of the Microsoft Corporation Modbus Registered trademark of the Modbus IDA Hopkinton MA USA Java Registered trademark of Su...

Страница 9: ...s must be provided by the location in which the Tankvision Gauge Link is installed 4 2 Electrical ratings Property Specification Operating Temperature 40 to 60 C 40 to 140 F Storage Temperature 40 to...

Страница 10: ...circuits or to cables feeding motors or other high current loads or near to contactors variable frequency drives inverters or frequency converters or other switchgear controlgear which may emit signif...

Страница 11: ...il the body of the enclosure is released from the top of the rail then turn the enclosure forwards away from the mounting rail All electrical connections and controls are available on the front panel...

Страница 12: ...the stripped wire end to be inserted The terminals will accept 0 2 to 2 5 mm2 24 to 14 AWG insulated wires which should be stripped 10 mm After insertion of the wire ensure that no bare conductor is...

Страница 13: ...ines and the C common connection Note that the polarity of the A B data signals is in accordance with the EIA TIA 485 standard Many third party devices with RS 485 interfaces have the sense of the A B...

Страница 14: ...iagnostic service_port_connections PC Service laptop PC or similar TVGL Tanvision Gauge Link R Required connection O Optional connection Note that in the case of Tankvision Gauge Links on a multi drop...

Страница 15: ...ved using LK_G links gain is described in detail further in the manual A link Gain control bit 0 default open B link Gain control bit 1 default open C link Gain control bit 2 default open Main Process...

Страница 16: ...The Tankvision Gauge Link has two POWER LEDs one for the main processor and one for the field bus interface The main processor LED is green and the field bus LED is yellow These should both be lit dur...

Страница 17: ...eywell Enraf and Emerson SAAB gauges must be done separately by a competent engineer Once the Tankvision Gauge Link has been connected the diagnostic port and the terminal emulation program has been s...

Страница 18: ...aved in Tankvision Gauge Link flash memory so when the unit is powered down and back up the configuration will remain 7 1 4 Commands INFO return This command prints the information shown in the above...

Страница 19: ...d GPUGAIN 7 return RS485 X return RS485 X return Where X is represents Y yes or N no These commands allow the user to enable the 910R bias resistors to pull the A and B lines to 5V and 0 volts This is...

Страница 20: ...lue into the holding register the cursor in the terminal emulation program will go to the start of the next line and wait for another value to be entered into the holding register If no more values ar...

Страница 21: ...cks are the blocks of registers detailed in the Tankvision Gauge Link Modbus Map document It can be seen at the top of each column shows which block of 100 registers is detailed Down the left side the...

Страница 22: ...This parameter is used if you require to remove a gauge from the system All gauges above this gauge will be automatically shuffled down and fill the space which was originally blanked 2nd gauge Gauge...

Страница 23: ...eed to be set back to Ensite mode by using the above command If Ensite is not polling for data when in this mode the Tankvision Gauge Link will then starting poll for normal data as configured in its...

Страница 24: ...generally the transmitted and received data will be printed on the same line per gauge a new line will be printed for a different gauge If the Field port is a TRL 2 port then the data printed will be...

Страница 25: ...egisters The reason for this is that different parameters can come from different devices with different addresses This allows data from different addresses to be mapped to the group of input register...

Страница 26: ...es is the same as configuring Honeywell Enraf devices in that the level address comes from holding registers 0 31 and temperature address comes from holding registers 100 131 The temperature elements...

Страница 27: ...and temp Gauge type 854 Gauge address 2 needs level and temp Gauge type 873 Gauge address 5 needs level temp temp elements water dip and density Gauge type 854 Gauge address 9 needs level Temp and it...

Страница 28: ...re the Tankvision Gauge Link is the TRL 2 version CONFIG return Enable configuration 0 1 return Level address 1 modbus address 1 100 1 return Temp address 1 1100 83 return Gauge type is a servo 83 1 2...

Страница 29: ...ddress 7 102 7 return Temp address 7 302 7 return Water register 07 from address 7 902 38 return Product pressure register 38 from address 7 3 8 return Level address 8 modbus address 8 103 108 return...

Страница 30: ...evel address 5 modbus address 5 104 5 return Temp address 5 1104 78 return Gauge type is a NRF590 78 5 6 return Level address 6 modbus address 6 105 6 return Temp address 6 1105 78 return Gauge type i...

Страница 31: ...1 100 1 return Temp address 1 1100 82 return Gauge type is a RADAR 82 1 2 return Level address 2 modbus address 2 101 2 return Temp address 2 1101 82 return Gauge type is a RADAR 82 2 3 return Level...

Страница 32: ...eturn Level address 3 modbus address 3 1102 83 return Gauge type is a SERVO 83 3 4 return Level address 4 modbus address 4 1103 83 return Gauge type is a SERVO 83 return Enter Result HTS 9600 return H...

Страница 33: ...4 The address when configuring the Tankvision Gauge Link is default 247 or any of the addresses configured in holding registers 0 31 The only parameters which can not be configured through the modbus...

Страница 34: ...ed in the Modbus specification document These parameters must be setup in the appropriate gauge such as the high and low alarms The Tankvision Gauge Link has a heartbeat and various information regist...

Страница 35: ...Details of firmware updates will be supplied if firmware updates are required in the future 8 2 Fault finding chart Parameter Setting Baud rate 9600 Baud Data bits 8 Parity none Stop bits 1 Flow cont...

Страница 36: ...rt TRANSMIT LED flickers but no activity on RECEIVE LED Incorrect configuration wrong field bus interface wrong communications parameters Baud rate etc wrong protocol wrong gauge addresses Investigate...

Страница 37: ...on Gauge Link until it is certain that all foreign object debris or contamination has been completely removed from the enclosure On first power up check for signs of unusual or incorrect operation bur...

Страница 38: ...mental conditions 9 F Fault finding chart 35 Field port connections 13 Foreign object liquid ingress 37 Functional earthing terminal 13 H Honeywell Enraf Fieldbus 26 Host port connections 13 I Icons 3...

Страница 39: ...Tankvision Gauge Link Endress Hauser 39...

Страница 40: ...www addresses endress com 71260205...

Отзывы: