Note!
Depending on the version, 4 to 10 current, PFM, pulse and RTD inputs are available in the energy
computer to record the flow, temperature and pressure signals.
Flow inputs
The Energy Manager processes all common flow measurement methods (volume, mass, differential
pressure). You can connect up to three flow transmitters at the same time. There is also the option
of using just one flow transmitter in various applications, see ’Terminals’ menu item).
Special flow meters
Item for very exact flow based on differential pressure method with compensation calculation as per
ISO 5167 as well as splitting range function for extending the measuring range, e.g. for orifice
measurement (up to three DP transmitters) and possibility of computing the mean value from
several DPTs.
Pressure inputs
A maximum of three pressure sensors can be connected. One sensor can also be used for two or all
three applications, see the ’Terminal’ item in the related table.
Temperature inputs
For connecting between two and six (max.) temperature sensors (RTD). A sensor can be used in
several applications here, see the ’Terminal’ item in the related table.
Flow inputs
Function (menu item)
Parameter setting
Description
Flow inputs
Flow 1, 2, 3
Configuration of individual flow transmitters.
Identifier
Name of the flow transmitter (max. 12 characters).
Flow measurement device
Volumetric
Mass
Setting of the measuring principle of your flow transmitter or as
to whether the flow signal is in proportion to the volume, (e.g.
vortex, EFM, turbine) or mass (e.g. Coriolis).
(For details, see Section 11.2 'Flow measurement
configuration')
Signal
Select
4-20 mA
0-20 mA
PFM
Pulse
Default
Selects the signal of the flow transmitter.
Terminals
None
A-10; A-110; B-112;
B-113; C-112; C-113; D-
112; D-113
Defines the terminal to which the flow transmitter in question
is connected. It is possible to use a transmitter (flow signal) for
several applications. For this, in the application in question,
select the terminal where the transmitter is located (multiple
selection possible).
Curve
Linear
Sqr. root
Select the curve of the flow transmitter used.
Unit
l/...; hl/...; dm
3
/...;
m
3
/
...
; bbl/...; gal/...; igal/...;
ft
3
/...; acf/...
Flow unit in format:
selected unit
by X
!
Note!
Only visible if the "Random" system unit has been selected.
kg, t, lb, ton (US)
Can only be selected for flow transmitter/mass
Time base
.../s; .../min;
.../h
; .../d
Time basis for the flow unit in the format:
X per time unit
selected.
!
Note!
Only visible if the "Random" system unit has been selected.