RMS621
Commissioning
Hauser
49
Relay/set point
Relays or passive digital outputs (open collector) are available in the relay for limit functions.
Depending on the version, 1 to 13 limit values (set points) are available.
Simulation
0.0 Hz - 0.1 Hz - 1.0 Hz -
5.0 Hz - 10 Hz - 50 Hz -
100 Hz - 200 Hz - 500 Hz
- 1000 Hz - 2000 Hz
Off
The function of the pulse output is simulated with this setting.
Simulation is active if the setting is not "off". Simulation ends if
you leave this item.
Function (menu item)
Parameter setting
Description
Identifier
Set point 1 to 13
An identifier can be assigned to the set point in question for a
better overview (max. 12 characters).
Transmit by
Display
Relay
Digital
Select
Assigns where the set point is output (passive digital output
only available with extension card).
Terminals
A-52, B-142, B-152,
C-142, C-152, D-142, D-
152
B-135, B-137, C-135, C-
137, D-135, D-137
None
Defines the terminal of the set point selected.
Relay: terminals X-14X, X-15X
Digital: terminals X-13X
Op. mode
Max+Alarm,
Grad.+Alarm, Alarm, Min,
Max, Gradient, Wet steam
alarm, Unit failure
Min+Alarm
Definition of the event which should activate the set point.
•
Min+Alarm
Minimum safety, event report when set point is undershot
with simultaneous signal source monitoring to NAMUR
NE43.
•
Max+Alarm
Maximum safety, event report when set point is overshot
with simultaneous signal source monitoring to NAMUR
NE43.
•
Grad.+Alarm
Gradient analysis, event report when set signal change is
overshot per time unit of the signal source with
simultaneous signal source monitoring to NAMUR NE43.
•
Alarm
Signal source monitoring to NAMUR NE43, no set point
function.
•
Min
Event report when set point is undershot without taking
NAMUR NE43 into consideration.
•
Max
Event report when set point is overshot without taking
NAMUR NE43 into consideration.
•
Gradient
Gradient analysis, event report when set signal change is
overshot per time unit of the signal source without taking
NAMUR NE43 into account.
•
Wet steam alarm
Relay (output) switches in the event of a wet steam alarm (2
C above saturated steam temperature).
•
Unit failure
Relay (output) switches if a device fault is present (fault
message).
Sig. source
Flow 1, Heat flow 1, Mass
sum 1, Flow 2, etc.
Select
Signal sources for the selected set point.
!
Note!
The number of signal sources depends on the number of
configured applications and inputs.
Swit. point
-99999 to 99999
0.0
Smallest output value of the analog output.
Function (menu item)
Parameter setting
Description