Appendix
RMA42
54
Hauser
Signal range
4-20mA
, 4-20mA squar,
0-20mA, 0-20mA squar,
0-10V
, 0-10V squar,
0-5V, 2-10V, 1-5V,
1-5V squar, 0-1V,
0-1V squar, +/- 1V,
+/- 10V, +/- 30V,
+/- 100mV
Pt46GOST, Pt50GOST,
Pt100IEC
, Pt100JIS,
Pt100GOST, Pt500IEC,
Pt1000IEC, Ni100DIN,
Ni1000DIN,
Cu50GOST, Cu53GOST,
Cu100GOST
3000 Ohm
Type B,
Type J
, Type K,
Type N, Type R, Type S,
Type T, Type C, Type D,
Type L, Type L GOST,
Type U
Configures the input signal
Lower range
Only displayed if "Signal
type" = "Current" or
"Voltage" is set.
Numerical value
1)
0
Configures the measuring range lower limit
Upper range
Only displayed if "Signal
type" = "Current" or
"Voltage" is set.
Numerical value
1)
100
Configures the measuring range upper limit
Connection
Only displayed if "Signal
type" = "RTD" is set.
2-wire
3-wire
4-wire
Configures the connection type for RTD thermometers
Tag
Customized text, max.
12 digits
Channel name; TAG
i
the device designation for channel 1
Unit
Only displayed if "Signal
type" = "Current" or
"Voltage" is set.
Customized text, max. 5
digits
Unit of the channel
Temperature unit
Only displayed if "Signal
type" = "RTD" or "TC" is
set.
°C
°F
K
Configures the temperature unit
Offset
Numerical value
1)
0
Configures an offset
Ref junction
Only displayed if "Signal
type" = "TC" is set.
intern
fixed
Configures the reference temperature
Fixed ref junc
Only visible if "fixed"
was selected for the
"Ref junction".
Numerical value
1)
Configures the constant reference temperature
Res minmax
No
Yes
Resets the min./max. values saved.
Analog in 2
Signal type
Off
Current
Voltage
RTD
TC
Configures the input type.
If "Signal type" is set to "Off", all the parameters under it are hidden.
Setup menu
1) Numerical values consist of 6 digits where the decimal point counts as a digit, e.g. +99.999