Commissioning
RMA42
32
Hauser
Namur NE43
Only for 4...20 mA. The measured value and the cables are monitored in accordance with NAMUR
NE43 recommendations. See
34 for this purpose. Default value: enabled
Open circ detect
Only for 1-5 V. Open circuit monitoring of the input.
Allow reset
If this function is activated, the min. and/or max. values can be reset outside the setup in the
Display menu. Active access protection does not lock resetting of this memory.
Output
É
Analog output 1/2
Failure mode:
• Min = Stored minimum value:
The stored minimum value is output.
• Max = Stored maximum value:
The stored maximum value is output.
• Fixed value = Constant value:
A constant value for output in the event of an error can be entered.
Output
É
Relay 1/2
Time delay
Setting the time delay for relay switching.
Operating mode
Operating mode of the relay:
• norm opened
• norm closed
Failure mode
• norm opened
• norm closed
"
Caution!
The failsafe mode of the limit relay is configured in the setup. If an input to which a limit value is
assigned experiences an error, the limit relay assumes the configured status. The effect of the limit
relay in the event of an error must be specified in the setup (energizes or de-energizes). If a failsafe
mode with a fixed error substitute value is configured in the input assigned, the corresponding relay
does not react to the error at the input. Instead it checks the substitute value for limit value violation
and switches depending on the limit value violation. The default value specifies that the relay is
energized.
Application
É
Calc value 1/2
Failure mode:
• Invalid:
The calculated value is not valid and is not output.
• Fixed value:
A constant value for output in the event of an error can be entered.