Wiring
RID14
16
Hauser
where the cable shielding is connected to the connector housing (e.g. pre-terminated
cables).
A
B
4
1
2
C
3
5
M20x1.5 /
NPT 1/2”
SW/AF 26
D
A0021497
8
Connectors for connection to the PROFIBUS® PA fieldbus
Pin assignment / color codes
A
Fieldbus connector
D 7/8" connector
D M12 connector
B
Field indicator
1 Brown wire: PA+ (terminal 1)
1 Gray wire: shielding
C
Connector on the housing
(male)
2 Green-yellow wire: grounding
2 Brown wire: PA+ (terminal 1)
3 Blue wire: PA- (terminal 2)
3 Blue wire: PA- (terminal 2)
4 Gray wire: shielding
4 Green-yellow wire: grounding
5 Positioning key
5 Positioning key
Technical data for connector:
• IP 67 degree of protection (NEMA 4x)
• Ambient temperature range: –40 to +105 °C (–40 to +221 °F)
5.3
PROFIBUS® PA cable specifications
5.3.1
Cable type
Twin-core cables are generally advisable for connecting the device to the fieldbus.
Following IEC 61158-2 (MBP), four cable types (A, B, C, D) can be used for FOUNDATION
Fieldbus™, only two of which (cable types A and B) are shielded.
• Cable types A or B are particularly preferable for new installations. Only these types have
cable shielding that guarantees adequate protection from electromagnetic interference
and thus the most reliable data transfer. In the case of cable type B, several fieldbuses
(same degree of protection) may be operated in one cable. No other circuits are
permissible in the same cable.
• Practical experience has shown that cable types C and D should not be used due to the
lack of shielding, since the freedom from interference frequently does not meet the
requirements described in the standard.