Operating Instructions

RID14

Fieldbus indicator

with PROFIBUS® PA protocol

0

10

20

30

40

50

BA01267K/09/EN/02.15

71288590

Содержание RID14

Страница 1: ...Products Solutions Services Operating Instructions RID14 Fieldbus indicator with PROFIBUS PA protocol 0 10 20 30 40 50 BA01267K 09 EN 02 15 71288590...

Страница 2: ......

Страница 3: ...9 5 5 Post connection check 19 6 Operating the field indicator 21 6 1 Quick operation guide 21 6 2 Display and operating elements 22 6 3 PROFIBUS technology 22 6 4 Configuration of the field indicator...

Страница 4: ...onal injury 1 2 2 Electrical symbols Symbol Meaning A0011197 Direct current A terminal to which DC voltage is applied or through which direct current flows A0011198 Alternating current A terminal to w...

Страница 5: ...ocumentation Reference to page Reference to graphic Series of steps Result of a sequence of actions Help in the event of a problem Visual inspection 1 2 4 Symbols in graphics Symbol Meaning 1 2 3 Item...

Страница 6: ...connection to a fieldbus The device is designed for installation in the field The manufacturer accepts no liability for damages resulting from incorrect use or use other than that designated Safe ope...

Страница 7: ...ted area observe the information on the nameplate 2 5 Product safety This measuring device is designed in accordance with good engineering practice to meet state of the art safety requirements has bee...

Страница 8: ...comprises Field indicator Brief Operating Instructions as hard copy ATEX safety instructions for using a device approved for hazardous areas optional Optional accessories e g pipe mounting bracket see...

Страница 9: ...dress Hauser 9 The field indicator has successfully passed the PROFIBUS PA physical layer test As a nonactive bus user it does interfere with Profibus data transfer Recognized component as per UL 3111...

Страница 10: ...n The original packaging provides optimum protection The permitted storage temperature range is 40 to 80 C 40 to 176 F it is possible to store the device in the limit temperature ranges for a limited...

Страница 11: ...cator 4 display positions can be fitted in 90 stages The display unit can be turned in 90 stages 1 First remove the cover clamp 1 and the housing cover 2 2 Then disconnect the display 3 from the elect...

Страница 12: ...on check After installing the device always run the following final checks Device condition and specifications Notes Is the device damaged Visual inspection Is the seal undamaged Visual inspection Is...

Страница 13: ...he display If other devices are connected this can result in the destruction of parts of the electronics Devices can be connected to the PROFIBUS PA in two ways Via a conventional cable gland Via a fi...

Страница 14: ...itch off power supply before installing or connecting the device It is recommended to ground the unit via one of the grounding screws If the shield of the fieldbus cable is grounded at more than one p...

Страница 15: ...ation is not interrupted Installation and maintenance are considerably easier Existing cable infrastructures can be used and extended immediately e g when creating new star distributor systems using 4...

Страница 16: ...e range 40 to 105 C 40 to 221 F 5 3 PROFIBUS PA cable specifications 5 3 1 Cable type Twin core cables are generally advisable for connecting the device to the fieldbus Following IEC 61158 2 MBP four...

Страница 17: ...2 Maximum overall cable length The maximum network expansion depends on the type of protection and the cable specifications The overall cable length combines the length of the main cable and the lengt...

Страница 18: ...eed side with capacitance termination at the field device Shielding at one end on the feed side Experience shows that the best results with regard to EMC are achieved in most cases in installations wi...

Страница 19: ...ce all unused cable entries with dummy plugs The cable entry seal may not be removed from the cable entry The housing cover and cable entry entries must be closed securely Install the device in such a...

Страница 20: ...RID14 20 Endress Hauser Electrical connection Notes Has the max length of the spurs as defined in the fieldbus specifications been observed Is the fieldbus cable completely shielded 90 and correctly g...

Страница 21: ...odule 25 Setting to specify whether operation is possible via DIP switches or remotely via the DTM Setting for the address of the bus users whose values are to be displayed Configuring an offset 1 2 3...

Страница 22: ...icator remains in the normal operational state If the status of the displayed value is uncertain quality code between 0x40 and below 0x80 the Uncertain measured value status symbol is lit If the statu...

Страница 23: ...signed to meet the needs of the process engineering sector Three features set it apart from a PROFIBUS DP system PROFIBUS PA supports operation in hazardous areas without any special requirements The...

Страница 24: ...vidual link It can be present in another link segment however For acyclic data exchange with a Class 2 master the link is virtually transparent Once the link address DP address and the device address...

Страница 25: ...plied via the bus if configuring the PROFIBUS PA indicator with the DTM via the CDI interface To ensure a connection to the device can be established operation must be set to Remote at the DIP switche...

Страница 26: ...lock symbol is lit on the display 6 5 2 Choosing between operation via DIP switches and remote operation When the device is operated via the DIP switches only 2 values are displayed even if more displ...

Страница 27: ...valid for the necessary Data Exchange Telegram The device displays a configuration error with this address 6 5 4 Configuring an offset Using the DIP switch it is possible to set the index offset of t...

Страница 28: ...the measures for troubleshooting can be found in Section Troubleshooting 31 Normal indicating mode commences as soon as the switch on procedure is completed Various measured values and or status value...

Страница 29: ...RID14 Maintenance Endress Hauser 29 8 Maintenance No special maintenance work is required on the device...

Страница 30: ...endress com 9 1 Device specific accessories 9 1 1 Cable glands and adapters Cable gland 2x Cable gland M20 RK01 AB Blanks blind 1 2 NPT 1 0718 51004490 M20x1 5 EEx d XP 51004489 G1 2 EEx d XP 5100491...

Страница 31: ...cs module defective Test with spare electronics module Order spare part Faulty connection to the fieldbus host system No connection can be made between the fieldbus host system and the indicator Check...

Страница 32: ...s between the values and the error message as follows e g channel 1 channel 2 and channel 3 are configured for value display Value of channel 1 error message value of channel 2 error message value of...

Страница 33: ...RID14 Item No Type Order number 2 Housing cover cpl display aluminum Ex d seal RIA141X HK Housing cover cpl display aluminum seal RIA141X HL Housing cover cpl display 316L Ex d FM XP CSA XP with seal...

Страница 34: ...ber on the nameplate and in the Operating Instructions indicates the device release XX YY ZZ example 01 02 01 XX Change to main version No longer compatible The device and Operating Instructions chang...

Страница 35: ...or ordered Legal specifications require Endress Hauser as an ISO certified company to follow certain procedures when handling products that are in contact with the medium To ensure safe swift and pro...

Страница 36: ...Disposal RID14 36 Endress Hauser 12 Disposal The device contains electronic components and must therefore be disposed of as electronic waste Comply with local disposal regulations...

Страница 37: ...on data in accordance with IEC 60079 11 FISCO Entity 13 1 4 Protocol specific data PROFIBUS PA Basic data Indicator for PROFIBUS PA can be used in conjunction with PROFILE 2 and PROFILE 3 3 0 3 01 and...

Страница 38: ...n No restrictions the orientation depends on the readability of the display 13 3 2 Mounting location Wall or pipe mounting see Accessories 13 4 Environment 13 4 1 Ambient temperature limits 40 to 80 C...

Страница 39: ...as to whether the devices used in laboratories and in distributed control systems are immune to interference thus increasing their functional safety ESD electrostatic discharge IEC 61000 4 2 6 kV cont...

Страница 40: ...l housing Electronics compartment and connection compartment together in single chamber housing Display can be fitted in 90 stages 13 5 2 Weight Aluminum housing Approx 1 6 kg 3 5 lb Stainless steel h...

Страница 41: ...nd messages 4 Communication symbol 5 Parameters cannot be modified symbol 6 Unit 7 Uncertain measured value status symbol Display range 99999 to 99999 DIP switches PROFIBUS PA Setting the bus address...

Страница 42: ...atibility EMC requirements NAMUR International user association of automation technology in process industries www namur de 13 7 4 CSA GP CSA General Purpose 13 8 Documentation System Components and D...

Страница 43: ...lues is specified using the Format display parameter Visible offline Yes Writable offline Yes Display value X submenu Navigation Operation Display value X Description Settings to display the measured...

Страница 44: ...Off Additional information Visible offline Yes Writable offline Yes Bargraph 0 Navigation Operation Display value X submenu Bargraph 0 Description Enter the minimum value 0 for the bargraph Only visi...

Страница 45: ...age with the highest priority is shown on the display This parameter is the input parameter for the NE107 module The category and the channel are encoded in the value Options GOOD Display overflow ch...

Страница 46: ...e Navigation Diagnostics Device information Device name Description Displays the device name Only read access Factory setting RID14 Additional information Visible offline Yes Writable offline No Devic...

Страница 47: ...ings Device reset Navigation Diagnostics Device information Device reset Device reset Description Use this function to reset the device configuration either entirely or in part to a defined state If s...

Страница 48: ...tion Visible offline No Writable offline No Display submenu Navigation Expert Display Description This submenu contains display settings Display duration Navigation Expert Display Display duration Des...

Страница 49: ...Use this function to enter a factor by which the measured value should be multiplied Only visible if data type analog Options 1E 06 1E 05 1E 04 1E 03 1E 02 1E 01 1E 00 1E 01 1E 02 1E 03 1E 04 1E 05 1E...

Страница 50: ...escription Displays general device information Extended order code Navigation Expert Diagnostics Device information Extended order code Description Displays the extended order code The extended order...

Страница 51: ...er 51 Navigation Expert Diagnostics Device information Manufacturer name Description Displays the manufacturer name Only read access Factory setting Endress Hauser Additional information Visible offli...

Страница 52: ...11 Wall 11 N Nameplate 8 Number of field devices 17 O Offset configuration 27 Operational safety 6 Overall cable length 17 P Parameter Access status tooling 47 Actual diagnostics count 45 Aktuelle Di...

Страница 53: ...u Device information 46 50 Device reset 47 Diagnostics 50 Display 48 Display value X 43 48 System 48 Switching write protection on off 26 System architecture 23 T Transport 10 Turning the display 11 W...

Страница 54: ......

Страница 55: ......

Страница 56: ...www addresses endress com...