Commissioning
Hauser
57
Navigation
"Setup" menu → Advanced setup → Administration → Def. access code
Structure of the submenu
Define access code
→
Define access code
Confirm access code
Defining the access code via local display
1. Navigate to the
Enter access code
parameter.
2. Define a max. 4-digit numeric code as an access code.
3. Enter the access code again to confirm the code.
The -symbol appears in front of all write-protected parameters.
The device automatically locks the write-protected parameters again if a key is not pressed for
10 minutes in the navigation and editing view. The device locks the write-protected
parameters automatically after 60 s if the user skips back to the operational display mode
from the navigation and editing view.
• If write access is activated via access code, it can be also be deactivated only via the
• The user role with which the user is currently logged on via the local display is
indicated by the
Access status display
parameter. Navigation path: "Operation" menu
→ Access stat.disp.
Defining the access code via the Web browser
1. Navigate to the
Enter access code
parameter.
2. Define a max. 4-digit numeric code as an access code.
3. Enter the access code again to confirm the code.
The Web browser switches to the login page.
If no action is performed for 10 minutes, the Web browser automatically returns to the
login page.
The user role with which the user is currently logged on via the Web browser is indicated
by the
Access status tooling
parameter. Navigation path: Operation → Access status
tooling
10.7.2
Write protection via write protection switch
Unlike write protection via user-specific access code, this allows write access to the entire
operating menu - other than the
"Contrast display" parameter
- to be locked.