Proline Promag W 400
Electrical connection
Hauser
27
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shielding
Copper braided shielding or braided shielding with foil shield. When grounding the
cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a
cable used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to
the "Media Planning and Installation Manual. EtherNet/IP" of the ODVA Organization.
Connecting cable for remote version
Electrode cable
Standard cable
3 ×0.38 mm
2
(20 AWG) with common, braided copper shield (
~
7 mm (0.28")) and
individually shielded cores
Cable for empty pipe
detection (EPD)
4 ×0.38 mm
2
(20 AWG) with common, braided copper shield (
~
7 mm (0.28")) and
individually shielded cores
Conductor resistance
≤50 Ω/km (0.015 Ω/ft)
Capacitance: core/shield
≤420 pF/m (128 pF/ft)
Operating temperature
–20 to +80 °C (–68 to +176 °F)
Coil current cable
Standard cable
2 ×0.75 mm
2
(18 AWG) with common, braided copper shield (
~
7 mm (0.28")) and
individually shielded cores
Conductor resistance
≤37 Ω/km (0.011 Ω/ft)
Capacitance: core/core,
shield grounded
≤120 pF/m (37 pF/ft)
Operating temperature
–20 to +80 °C (–68 to +176 °F)
Test voltage for cable
insulation
≤ AC 1433 V r.m.s. 50/60 Hz or ≥ DC 2026 V
Reinforced connecting cable
Use in the following situations:
• When laying the cable directly in the ground
• Where there is a risk of damage from rodents
• If using the device below IP68 degree of protection