Proline Promag W 400
Electrical connection
Hauser
31
7.1.6
Preparing the connecting cable for the remote version
When terminating the connecting cable, pay attention to the following points:
• In the case of electrode cables, make sure that the ferrules do not touch the core shields on
the sensor side. Minimum distance = 1 mm (exception: green “GND” cable)
• In the case of coil current cables, insulate one core of the three-core wire at the level of the
core reinforcement. You only require two cores for the connection.
• Fit the fine-wire cores with ferrules.
Transmitter
Electrode cable
Coil current cable
A
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
100 (3.94)*
B
GND
1
2
1
2
1
2
2
A0021324
9
Engineering unit mm (in)
A
90 (3.54)*
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
B
1
A0021325
10
Engineering unit mm (in)
A = Termination of the cables
B = Termination of the fine-wire cores with ferrules
1 = Red ferrules, 1.0 mm (0.04 in)
2 = White ferrules, 0.5 mm (0.02 in)
* = Stripping only for reinforced cables