Mycom S CPM 153
6 Start-up
Hauser
71
To enter the menu, proceed as follows:
⇒
⇒
PARAM
pH
7.00
Param
Settings
Set up 1
Set up 2
Manual operation
First start up
Edit
Next
E
Hold
pH
7.00
Param
Edit
Next
Set up 2
E
Hold
Controller settings
Check
Limit switch
Contr. quick adj.
Chemoclean
CODE
CHOICE
(default = bold)
INFO
O1
Weekly progr.
Clean trigger
Ext. Control
off
off
off
Select control levels
Select the function which will trigger ChemoClean
cleaning.
O2
Weekly progr.
Clean trigger
Ext. Control
off
off
off
Note in display:
Displays the current system status
O3
Weekly programme
User prg.
Select the configuration menu
Weekly programme
: Select only with "weekly pro-
gramme on"
User programme
: Here you create customer-specific
programmes using the programme editor (see pro-
gramme editor, p. 72).
Weekly programme:
OA1
Monday
Tuesday
.....
Sunday
1
2
...
0
Weekday selection menu
Select cleaning day. The number of cleaning triggers
for the day is shown behind each day.
OA2
Edit day?
Copy day?
Select day function
Edit day
: You can edit the function for this day.
Copy day
: The day which you have selected in field
OA1 is copied to the day selected in the following field.
Edit day:
OAA1
Clean
18:22 18:23
no progr.
View/edit day programme
You can see the complete day programme or "no
progr.". You can overwrite this point and the set pro-
grammes with a new selection.
The start and finish times are always given.
Example:
Clean
18:22 (start time) 18:23 (finish time)
User prog.: use of a programme you created (see
programme editor, p. 72)
OAA2
01 Water
02 +Cleaner
03 Water
04 Rep. cleaning
0s
30s
30s
0x
Select programme blocks
The times for individual programme steps can be
individually adjusted here. Select a block for editing by
pressing "E".
+Cleaner:
Cleaner will be delievered additional to
water.
Rep. cleaning
: Number of repeats of steps 01 to 03
!
Note!
• When you change one of this programme blocks the
changes will affect every cleaning.
• Leave this selection by pressing "PARAM".