8 Troubleshooting
Hauser
101
8.1.3
Instrument-specific error
Feed forward control
does not work
Additional module M3R-x missing
Additional module M3R-2 with 1 or
M3R-1 with 2 current inputs
See spare parts list in see Chap. 8.3
Incorrect version
Resistance input only permissable
with non-Ex.
Feedback input does
not work
Additional module M3R-x missing
See spare parts list in Chap. 8.3
Resistance input only permissible
with non-Ex.
Feedback incorrect
Feedback potentiometer outside
range
Smallest permissible potentiometer
1 kohm, largest permissible potentio-
meter 10 kohms
Feedback range not set or not set
correctly
Set lower and upper range value in
"PARAM" menu
Data cannot be saved
No DAT memory module available
DAT available as accessory, see
Chap. 9
Error
Possible cause
Remedial action
Equipment needed,
spare parts
Error
Possible cause
Tests and / or remedial
action
Equipment, spare parts,
personnel
Display dark, no LEDs
active
No mains voltage
Check whether mains voltage is
applied
Electrician / e.g. multimeter
Incorrect supply voltage or too low
Compare actual mains voltage with
nameplate rating
Connection defective
Terminal not picked-up; insulation
clamped
Instrument fuse defective (non-Ex)
Replace fuse after comparing mains
voltage and nameplate rating
Electrician / suitable fuse; see dia-
grams in Chap. 8.7
Instrument fuse defective (Ex instru-
ment)
Replace fuse
Use Ex fuse; electrician required
Power unit defective
Replace power unit, pay attention to
variant
On-site diagnosis: all 6 red LEDs on
the M3G module must be lit
Central module defective (if all 6
LEDs on the power unit M3G are lit)
Replace central module
pay attention to variant
On-site diagnosis by E+H Service
(test module required)
Ribbon cable loose or defective
Check ribbon cable
Cable soldered onto the site of the
M3G module
Display dark, but
LED active
Central module defective
(Module: M3Cx-x)
Replace central module M3Cx-x
On-site diagnosis by E+H Service
(test module required)
Display functioning, but
not change in display
and/or instrument can-
not be operated
Instrument or module in instrument
not correctly installed
Check module connections
see installation diagram page 105
Operating system in impermissible
state
Switch instrument off and on
poss. EMC problem: if problem per-
sists, have installation checked by
E+H Service
Instrument gets hot
Incorrect mains voltage or too high
Compare mains voltage and name-
plate rating
Power unit defective
Replace mainboard
all 6 red LEDs on the M3G module
must be lit