Liquiphant FTL64
Technical data
Hauser
61
Process pressure range of the sensors
[°C]
[bar]
[psi]
[°F]
p
e
T
p
0
-1
32
-14.5
-60
-76
100
1450
0
32
63
914
260 280
500 540
A0042363
Ordering information: Product Configurator, feature "Application":
• PN: max. 100 bar (1
450 psi) max. 230 °C (446 °F)
• PN: max. 100 bar (1
450 psi) max. 280 °C (536 °F)
• With PFA coating (conductive): max. 40 bar (580 psi) max. 230 °C (446 °F)
14.4.5 Test pressure
Test pressure = 1.5 · PN
• Maximum 100 bar (1
450 psi) at 230 °C (446 °F) and 280 °C (536 °F)
• Membrane burst pressure at 200 bar (2
900 psi)
The device function is limited during the pressure test.
The mechanical integrity is guaranteed at pressures up to 1.5 times the process nominal
pressure PN.
14.4.6 Density
Liquids with density > 0.7 g/cm
3
Switch position > 0.7 g/cm
3
(as-delivered state)
Liquids with density 0.5 g/cm
3
Switch position > 0.5 g/cm
3
(can be set via DIP switch)
Liquids with density > 0.4 g/cm
3
• Optionally available, not suitable for SIL applications
• Fixed value that cannot be edited
The function of the DIP switch is interrupted
For distinguishing between media/density detection, use the Liquiphant Density
(FEL60D) with a density computer.
14.4.7 Viscosity
≤ 10
000 mPa⋅s
14.4.8 Pressure tightness
Up to vacuum
In vacuum evaporation plants, select the 0.4 g/cm
3
density setting.
14.4.9 Solids contents
⌀ ≤ 5 mm (0.2 in)