Behavior of output signal
• OK status: output current 2.2 to 3.8 mA
• Demand mode: output current 0.4 to 1.0 mA
• Alarm: output current < 1.0 mA
Terminals
Terminals for cable cross-section up to 2.5 mm
2
(14 AWG). Use ferrules for the wires.
Overvoltage protection
Overvoltage category II
Terminal assignment
>0,5
COM
–
+
MIN
MAX
>0,7
IEC 60947-5-6
8,2 V DC NAMUR
1
2
L-
L+
.
-
1
2
!
!
4
3
1
2
1
3
4
M12
L+ L- PE
B
A
A0036066
27
2-wire NAMUR ≥ 2.2 mA/≤ 1.0 mA, electronic insert FEL68
A
Connection wiring with terminals
B
Connection wiring with M12 plug in housing according to EN61131-2 standard
Содержание Liquiphant FTL64