Operation
Liquiline System CA80PH
132
Hauser
Other settings and manual cleaning
Path: Menu/Setup/Additional functions/Cleaning/Cleaning 1 ... 4
Function
Options
Info
Start signal
Options
• Bus signals
• Signals of digital or
analog inputs
Factory setting
None
In addition to cyclic cleaning, you can also use an input
signal to start event-controlled cleaning.
Choose the trigger for such a cleaning process here.
Interval programs and weekly programs are executed as
normal, i.e. conflicts can occur. Priority is given to the
cleaning program that was the first to be started.
Hold
Options
• On
• Off
Factory setting
On
Decide whether there should be a hold during the
cleaning process. This hold affects the inputs to which
this cleaning process is assigned.
Start single
Action
Start an individual cleaning process with the selected
parameters.
If cyclical cleaning is enabled, there are times in which it
is not possible to manually start the process.
Manual mode
Action
You start the manual mode by acknowledging the war-
ning. You can now start each possible cleaning step
manually. If you want to return to cyclical cleaning, you
must set "Manual mode" to "Off".
Stop or Stop Failsafe
Action
End the cleaning process (cyclical or manual)
Output selection
Goes to the "Outputs" menu
You can assign the cleaning program directly to one or
more outputs.
--> "Outputs" section