Ecograph T, RSG35
Appendix
Hauser
149
Navigation
Expert → Application → Limits → Limit x → Channel/value
Direct access code: 450000-0xx
Examples: Set point 1: 450000-000; Set point 30: 450000-029
Description
Select which input/calculated value the limit value refers to.
Options
Switched off, Universal input x, Digital input x, Maths x
Factory setting
Switched off
Type
Navigation
Expert → Application → Limits → Limit x → Type
Direct access code: 450001-0xx
Examples: Set point 1: 450001-000; Set point 30: 450001-029
Description
Type of limit value (depends on the input variable).
Options
Switched off, Upper set point, Lower set point, Analysis x
Description of the individual set point types
Set point type/function
Description
Hysteresis
For every set point, the switch point can be controlled via a hysteresis.
The hysteresis is set as an absolute value (positive values only) in the unit of the respective channel (e.g. upper
set point = 100 m, hysteresis = 1 m: Set point on = 100 m, set point off = 99 m).
Upper set point
The limit value is active if the value exceeds the configured value. The limit value is switched off if the limit
value, including hysteresis, is undershot.
t
Measured value
Threshold
“off”
Hysteresis
Setpoint
Setpoint “on”
Setpoint “off”
A0010187-EN