Appendix
Ecograph T, RSG35
140
Hauser
User entry
Text (max. 22 characters)
Record duration
Navigation
Expert → Application → Maths → Maths x → Record duration
Direct access code: 400013-00x
Examples: Maths 1: 400013-000; Maths 4: 400013-003
Description
The duration between "On" and "Off" can be recorded. The duration is appended to the "Off"
event text (<hhhh>h<mm>:<ss>).
Power failure times do not affect the duration. If the digital channel was "on" before the
power failure and is still "on" after the power failure, the duration continues.
Only visible if the result is = control input or state.
Options
No, Yes
Factory setting
No
Zoom start
Navigation
Expert → Application → Maths → Maths x → Zoom start
Direct access code: 400016-00x
Examples: Maths 1: 400016-000; Maths 4: 400016-003
Description
If the whole value range is not used, you can configure the lower value of the required
section here. Zooming does not affect the save function.
Only visible if the result is = instantaneous value.
User entry
Number (max. 8 digits)
Factory setting
0
Zoom end
Navigation
Expert → Application → Maths → Maths x → Zoom end
Direct access code: 400017-00x
Examples: Maths 1: 400017-000; Maths 4: 400017-003
Description
Like "Zoom start". However, enter the upper value of the required range here.
Only visible if the result is = instantaneous value.
User entry
Number (max. 8 digits)
Factory setting
100