Ecograph T, RSG35
Appendix
Hauser
133
Modbus
Navigation
Expert → Communication → Modbus Slave → Modbus
Direct access code: 480000-000
Description
Specify the physical interface you wish to use.
Options
Not used, RS485, Ethernet
Factory setting
Not used
Unit address
Navigation
Expert → Communication → Modbus Slave → Unit address
Direct access code: 480001-000
Description
Enter the device address where it should be possible to reach this device in the bus.
Only visible if Modbus = RS485.
User entry
1 to 247
Factory setting
1
Port
Navigation
Expert → Communication → Modbus Slave → Port
Direct access code: 480004-000
Description
Port via which the Modbus protocol can be activated.
Only visible if Modbus = Ethernet.
User entry
Number (max. 5 digits)
Factory setting
502
"Serial interface" submenu
Navigation
Expert → Communication → Modbus Slave → Serial interface
Description
Contains settings for the serial interface.
Only visible if Modbus = RS485.
Baud rate