Decimal point
Navigation
Expert → Application → Maths → Maths x → Decimal point
Direct access code: 400005-000
Examples: Maths 1: 400005-000; Maths 4: 400005-003
Description
Number of places after decimal point for the display.
Only visible if function = formula editor and the result is = instantaneous value or counter.
Options
None, One (X.Y), Two (X.YY), Three (X.YYY), Four (X.YYYY), Five (X.YYYYY)
Factory setting
One (X.Y)
Action
Navigation
Expert → Application → Maths → Maths x → Action
Direct access code: 400006-000
Examples: Maths 1: 400006-000; Maths 4: 400006-003
Description
Set up the function of the control input.
Only visible if the result is = control input.
Action
Description
Start/stop recording
The device only saves data as long as a high signal is present.
Screensaver on
Switches backlight/display off, low = off, high = on.
Lock setup
The user can only change the setup if a low signal is present.
Time synchronization
If a high signal is applied, the device rounds the system time up or down (only for
low→high change) to the nearest minute: 0 to 29 → Round down; 30 to 59 →
round up.
Set point monitoring
on/off
The entire set point monitoring function of the device can be switched on (for
"high") or switched off (for "low").
Block keyboard/navigator The device can only be operated if a low signal is present. Otherwise all key
activation and navigator actions are discarded.
Start/stop analysis 1
Starts/ends the external analysis (the analysis only runs as long as the signal is
high). Measured value acquisition for the graphic display continues.
Options
Switched off, Start/stop recording, Screensaver on, Block set up, Time synchronization, Set
point monitoring on/off, Block keyboard/navigator, Start/stop analysis 1
Factory setting
Switched off
Switches relay