Deltatop DP71B, DP72B, DP73B
Installation
Hauser
11
"
Caution!
For flow measurements in vertical pipes, the primary device should be mounted at a position with
upward flow. This prevents partial emptying of the pipe during measurement.
3.4
Mounting position for gas applications
With gas applications, the transmitter must be mounted above the pipe. All impulse pipes must be
installed with a slope of at least 1:15 to the process connection - coming from the transmitter. This
ensures that any condensate flows back into the process pipe and thus does not influence the
measurement.
!
Note!
When measuring in humid gases, installation of condensate separators (5) and drain valves (6) is
useful for capturing and removing condensate.
P01-DPxxxxxx-11-xx-xx-xx-006
A: Preferred configuration B: Alternative configuration (if the transmitter cannot be mounted above the pipe)
1: Pitot tube 2: Shut-off valves 3: Three-valve manifold 4: Deltabar differential pressure transmitter 5: Separator 6: Drain
valve
+
–
1
2
3
4
A
1
3
2
B
4
+
–
5
6
5
6
2
Compact; vertical
1)
Compact; horizontal
2)
Remote; vertical
Remote; horizontal
flow upwards
DP7xB-CV...
P01-DP61Dxxx-11-00-00-xx-001
mounting left
DP7xB-CB...
P01-DP61Dxxx-11-00-00-xx-007
upwards/downwards
DP7xB-BW...
P01-DP61Dxxx-11-00-00-xx-013
top/bottom
DP7xB-BD...
P01-DP61Dxxx-11-00-00-xx-016
flow downwards
DP7xB-CU...
P01-DP61Dxxx-11-00-00-xx-002
mounting right
DP7xB-CC...
P01-DP61Dxxx-11-00-00-xx-008
1)
Recommended housing version for the Deltabar S: T14 (for use of the Deltabar display)
2)
Recommended housing version for the Deltabar S: T15 (for use of the Deltabar display)