Description of device parameters
Deltabar FMD71, FMD72
56
Reset peakhold (161)
Navigation
Expert → Diagnosis → Reset peakhold (161)
Write permission
Service engineers/Expert
Description
You can reset the peak indicators with this parameter.
Options
• Cancel
• Pressure HP
• Pressure LP
• Sensor Temp. HP
• Sensor Temp. LP
• All
Factory setting
Cancel
Operating hours (162)
Navigation
Expert → Diagnosis → Operating Hours (162)
Write permission
No write permissions. Parameter is read only.
Description
Displays the hours of operation. This parameter cannot be reset.
Damping switch (164)
Navigation
Expert → Measurement → Basic setup → Damping switch (164)
Write permission
No write permissions. Parameter is read only.
Description
Displays the switch position of DIP switch 2 which is used to switch the damping of the
output signal on and off.
Display
• Off
The output signal is not damped.
• On
The output signal is damped. The attenuation constant is specified in the "Damping"
(017) (184) parameter
Factory setting
On
Alarm cur.switch (165)