background image

Deltabar FMD71, FMD72

Description of device parameters

63

Write permission

No write permissions. Parameter is read only.

Description

Displays the measured pressure before the sensor trim.

Meas. press. HP (281)

Navigation

 

Expert → Measurement → Pressure → Meas. Press. HP (281)

Write permission

No write permissions. Parameter is read only.

Description

Displays the measured HP pressure after sensor trim and simulation.

Meas. press. LP (282)

Navigation

 

Expert → Measurement → Pressure → Meas. Press. LP (282)

Write permission

No write permissions. Parameter is read only.

Description

Displays the measured LP pressure after sensor trim and simulation.

Sensor Temp. LP (283)

Navigation

 

Expert → Measurement → Basic setup → Sensor Temp. LP (283)

Write permission

No write permissions. Parameter is read only.

Description

Displays the temperature currently measured in the sensor module. This can deviate from

the process temperature.

Sim. Press. HP (284)

Navigation

 

Expert → Diagnosis → Simulation → Sim. Press. HP (284)

Write permission

Operators/Service engineers/Expert

Description

Enter the simulation value. See also "Simulation Mode".

Prerequisite

"Simulation Mode" = Pressure HP

Value at switch-on

Current pressure measured value

Содержание Deltabar FMD71

Страница 1: ...scription of device parameters Deltabar FMD71 FMD72 Electronic differential pressure for level measurement Differential pressure transmitter with ceramic and metal sensors GP01013P 00 EN 03 12 7120028...

Страница 2: ......

Страница 3: ...2 Structure of the operating menu 7 2 3 Operating options 8 2 4 Operating the device using onsite display optional 8 2 5 Operation using Endress Hauser operating program 11 2 6 Direct access to parame...

Страница 4: ...sioning Operating Instructions BA01044P your comprehensive reference These Operating Instructions contain all the information that is required in various phases of the life cycle of the device from pr...

Страница 5: ...Alternating current A terminal to which alternating voltage is applied or through which alternating current flows A0017381 Direct current and alternating current A terminal to which alternating volta...

Страница 6: ...a the local display A0013143 Operation via operating tool Indicates navigation to the parameter via the operating tool A0013144 Write protected parameter Indicates a parameter that can be locked again...

Страница 7: ...equired for this purpose time and again In addition to technical process oriented tasks experts can also perform administrative tasks e g user administration Experts can avail of the entire parameter...

Страница 8: ...all device parameters that neither affect measurement nor integration into a distributed control system Measurement Contains all parameters for configuring the measurement Output Contains all paramete...

Страница 9: ...rs etc Quick and safe commissioning 2 4 1 Setting the contrast on the display module and press simultaneously increases the contrast and press simultaneously decreases the contrast 2 4 2 Overview 1 3...

Страница 10: ...acters within a function A0017881 Confirm entry Jump to the next item Selection of a menu item and activation of edit mode A0017879 and A0017881 Contrast setting of onsite display darker A0017880 and...

Страница 11: ...ged The mbar unit is defined in another parameter and cannot be changed here 1 1 0 0 0 0 0 mbar Press or to get to edit mode The first digit is highlighted in black 2 1 0 0 0 0 0 mbar Use the key to c...

Страница 12: ...d all the parameters you can lock your entries against unauthorized and undesired access You have the following options for locking unlocking operation Via the DIP switch on the electronic insert loca...

Страница 13: ...tup Advanced Setup Code Definition Read permission Operators Service engineers Expert Write permission Operators Service engineers Expert Description Use this function to enter a release code with whi...

Страница 14: ...t This code resets all the parameters apart from Device tag 022 Linearization table Operating hours 162 Event logbook Curr trim 4 mA 135 Curr trim 20 mA 136 Lo trim sensor 131 Hi trim sensor 132 Lo tr...

Страница 15: ...care and PDM Prerequisite DIP switch set to SW and Damping set to on If you download using the factory setting Configuration copy all parameters required for a measurement will be downloaded The funct...

Страница 16: ...d only 120 44 Operator code 021 27 Expert System Device Information Direct access Description Cust tag number 254 58 Device tag 022 28 Serial number read only 096 39 Firmware version read only 095 38...

Страница 17: ...HP read only 109 41 Sensor press LP read only 280 62 Meas press HP read only 281 63 Meas press LP read only 282 63 Corrected press read only 172 57 Expert Measurement Level Direct access Description...

Страница 18: ...40 Expert Measurement Sensor Limits Lp Direct access Description LRL sensor 272 61 URL sensor 273 61 Expert Measurement Sensor Trim HP Direct access Description Lo trim measured 129 46 Hi trim measur...

Страница 19: ...Current mode 144 50 Bus address 145 50 Preamble number 146 51 Expert Communication HART Info Direct access Description Device ID read only 279 62 Device Revision read only 108 40 Manufacturer ID read...

Страница 20: ...ss LP 290 65 Operating hours read only 162 56 Config counter read only 100 40 Sensor changes read only 287 64 Expert Diagnostics Sensor HP Direct access Description Min meas press read only 073 37 Cou...

Страница 21: ...stic 10 read only 084 38 Expert Diagnostics Event Logbook Direct access Description Last diag 1 read only 085 38 Last diag 2 read only 086 38 Last diag 3 read only 087 38 Last diag 4 read only 088 38...

Страница 22: ...uage as selected when ordering the device Possibly a third language language of the manufacturing plant Factory setting English Display mode 001 Navigation Expert System Display Display mode 001 Write...

Страница 23: ...ber of places after the decimal point for the value displayed in the main line Options Auto x x x x xx x xxx x xxxx x xxxxx Factory setting Auto Measuring mode 005 182 Navigation Expert Measurement Me...

Страница 24: ...el Calib Offset 008 Navigation Expert Measurement Basic Setup Calib Offset 008 Write permission Service engineers Expert Description Position adjustment the pressure difference between the set point a...

Страница 25: ...bration the level vessel full must actually be available The associated pressure is then automatically recorded by the device In the case of dry calibration the level vessel full does not have to be a...

Страница 26: ...applied pressure value Prerequisite Pressure measuring mode Options Cancel Confirm Factory setting Cancel Get URV 016 Navigation Expert Output Current Output Get URV 016 Write permission Operators Ser...

Страница 27: ...ly Description Displays the level value prior to linearization Meas Diff Press 020 Navigation Expert Measurement Pressure Meas Diff Press 020 Write permission No write permissions Parameter is read on...

Страница 28: ...e number 5864 Factory setting 0 Device tag 022 Navigation Expert System Instrument info Device tag 022 Write permission Operators Service engineers Expert Description Enter the device tag e g TAG numb...

Страница 29: ...t Measurement Level Level Before Lin 025 Write permission Operators Service engineers Expert Description Select the unit for the measured value display for the level before linearization Example Curre...

Страница 30: ...owing parameters Empty Calib Empty Pressure Empty Height Full Calib Full Pressure Full Height Factory setting Wet Empty Calib 028 011 Navigation Expert Measurement Level Empty Calib 028 011 Write perm...

Страница 31: ...erequisite Level Selection In height Calibration mode Dry entry Calibration mode Wet display Factory setting 0 0 Full Calib 031 012 Navigation Expert Measurement Level Full Calib 031 012 Write permiss...

Страница 32: ...xpert Description Enter the height value for the upper calibration point vessel full The unit is selected via the Height unit parameter Prerequisite Level Selection In height Calibration mode Dry entr...

Страница 33: ...rt Description Select the linearization mode Options Linear The level is output without being converted beforehand Level before Lin is output Erase table The existing linearization table is deleted Ma...

Страница 34: ...alue 040 123 193 Write permission Operators Service engineers Expert Description Enter the X value level before linearization for the specific point in the table and confirm Note If Lin mode Manual th...

Страница 35: ...the Insert point option via the Edit table parameter Point 5 is displayed for the Line numb parameter Enter new values for the X val and Y val parameters Delete point in this case the 5th point for ex...

Страница 36: ...the setting of the High Alarm Curr parameter 052 Factory setting Warning High Alarm Curr 052 Navigation Expert Output Current Output High Alarm Curr 052 Write permission Operators Service engineers Ex...

Страница 37: ...at occurred and was rectified Note Digital communication the last message is displayed Use the Reset logbook parameter to clear the messages listed in the parameter Last diag code Min meas press 073 N...

Страница 38: ...st diag 3 087 Last diag 4 088 Last diag 5 089 Last diag 6 090 Last diag 7 091 Last diag 8 092 Last diag 9 093 Last diag 10 094 Navigation Expert Diagnostics Event logbook Write permission No write per...

Страница 39: ...7 Write permission Parameter is read only Only Endress Hauser Service has write permission Description Displays extended order number Factory setting According to order specifications Order code 098 N...

Страница 40: ...rmissions Parameter is read only Description Displays the lower range limit of the sensor module URL sensor 102 Navigation Expert Measurement Sens Limit HP LRL sensor 101 Write permission No write per...

Страница 41: ...ion Expert Diagnosis Simulation Simulation mode 112 Write permission Operators Service engineers Expert Description Switch on simulation and select the simulation mode When changing the measuring mode...

Страница 42: ...T Tank content Only level measuring mode Simulation Error number Measuring mode Linearization mode Diagnostics device status Simulation current Measured differential pressure P Level before lineariza...

Страница 43: ...xpert Description Enter the simulation value See also Simulation Mode Prerequisite Measuring Mode level Lin mode Activate table and Simulation Mode Tank content Value at switch on Current tank content...

Страница 44: ...h 120 Write permission Expert Description Displays the status of DIP switch 1 on the electronic insert You can lock or unlock parameters relevant to the measured value with DIP switch 1 If operation i...

Страница 45: ...ory settings reset section 13 Factory setting 0 Press Eng Unit 125 Navigation Expert Measurement Basic setup Press Eng Unit 125 Write permission Operators Service engineers Expert Description Select t...

Страница 46: ...rocess Density parameters Options g cm3 kg m3 kg dm3 lb in3 lb ft3 Factory setting g cm3 Electronics temp 128 Navigation Expert Measurement Basic setup Electronics Temp 128 Write permission No write p...

Страница 47: ...present for the lower calibration point Hi trim sensor 132 Navigation Expert Measurement Sensor Trim HP Hi Trim Sensor 132 Write permission No write permissions Parameter is read only Description Sens...

Страница 48: ...im 20mA 136 Write permission Service engineers Expert Description Enter the pressure value for the upper point 20 mA of the current partial regression lines Using this parameter and Curr Trim 4 mA you...

Страница 49: ...description max 16 alphanumeric characters HART message 140 Navigation Expert Communication HART info HART message 140 Write permission Service engineers Expert Description Enter the message max 32 al...

Страница 50: ...Press HP 281 Sensor Press HP 109 and Sensor Temp HP 110 33 HART command 33 Default output Meas Diff Press 020 Meas Press HP 281 Sensor Press HP 109 and Sensor Temp HP 110 Factory setting 1 HART comman...

Страница 51: ...h modem component could swallow one byte at least 2 bytes must be the preamble Input range 2 20 Factory setting 5 Primary Value Is 147 Navigation Expert Communication HART Output Primary Value Is 147...

Страница 52: ...ng on the selected measuring mode the following measured values can be displayed Measured value Measuring mode Measured differential pressure Level pressure Corrected pressure Level pressure Measured...

Страница 53: ...Corrected pressure Level pressure Measured pressure HP Level pressure Sensor press HP Level pressure Sensor temperature HP Level pressure Measured pressure LP Level pressure Sensor press LP Level pres...

Страница 54: ...ssure Sensor temperature HP Level pressure Measured pressure LP Level pressure Sensor press LP Level pressure Sensor temperature LP Level pressure Level before linearization Level Tank content Level P...

Страница 55: ...m 157 Navigation Expert System Display HART Input Form 157 Write permission Operators Service engineers Expert Description Number of decimal places of the displayed input value Options x x x xx x xxx...

Страница 56: ...162 Write permission No write permissions Parameter is read only Description Displays the hours of operation This parameter cannot be reset Damping switch 164 Navigation Expert Measurement Basic setup...

Страница 57: ...permission No write permissions Parameter is read only 6 Description Displays the measured differential pressure after position adjustment Tank description 173 Navigation Expert Measurement Linearizat...

Страница 58: ...Current at alarm 051 190 Write permission Operators Service engineers Expert Description Select Output fail mode In case of an alarm the current and the bargraph assume the current value specified wi...

Страница 59: ...ensor module nominal value 10 of upper sensor module nominal value You can reset this value using the Reset Peakhold 161 parameter MIN MEAS TEMP 264 Navigation Expert Diagnosis Sensor HP Min Meas Temp...

Страница 60: ...o write permissions Parameter is read only Description Displays the highest pressure value measured peakhold indicator You can reset this peak indicator via the Reset peakhold 161 parameter COUNTER P...

Страница 61: ...limit of the sensor module URL sensor 273 Navigation Experts Measurement Sens Limit LP URL Sensor 273 Write permission No write permissions Parameter is read only Description Displays the upper range...

Страница 62: ...ure while simultaneously and automatically accepting a reference pressure present for the lower calibration point Hi trim sensor 278 Navigation Expert Measurement Sensor Trim LP Hi Trim Sensor 278 Wri...

Страница 63: ...permission No write permissions Parameter is read only Description Displays the measured LP pressure after sensor trim and simulation Sensor Temp LP 283 Navigation Expert Measurement Basic setup Sens...

Страница 64: ...Description Determine the transmitter connection After both sensor modules are replaced or if the main electronics fail the configuration has to be redefined using this parameter Options At sensor HP...

Страница 65: ...89 Navigation Expert Diagnosis Pmax process LP 289 Write permission Operators Service engineers Expert Description Customer specific process detection limit upper for sensor module LP Factory setting...

Страница 66: ...38 Diagnostic 9 083 38 Diagnostic 10 084 38 Direct access 119 44 Display mode 001 22 Display module contrast 9 E Edit table 042 35 Electr serial no 121 44 Electronics temp 128 46 Empty Calib 011 28 2...

Страница 67: ...5 Pmin process LP 290 65 Pos Zero Adjust 007 24 Preamble Number 146 51 Press Eng Unit 125 45 Primary Value 148 51 Primary Value Is 147 51 Process Density 035 32 R Reset logbook 159 55 Reset peakhold 1...

Страница 68: ...www addresses endress com 71200289 71200289...

Отзывы: