Configure Mail
Recipients –
Mail
Addresses
Index
1
1, 2, 3, 4
Selects the mail recipients
table index to configure.
Configure Mail
Recipients –
Recipient Mail
Address
Blank
User
configurable
Sets a mail recipients mail
address.
Configure Mail
Recipients –
Enable
Recipient
False
False, True
Enables a mail recipient.
Send Test Mail
Sends a test message to the
message recipient selected
by the Mail Addresses Index.
UPS Configuration
Auto Output
True
True, False
Automatically determines
input Voltage and Frequency
to use during UPS mode.
Output Voltage
Level
208V
208V, 230V,
240V
Sets the output voltage level
if Auto Output is false.
RS232
Baudrate
9600
9600, 19200,
38400,
57600,
115200
Sets the RS232 baudrate.
Output
Frequency
60 Hz
50 Hz, 60 Hz
Sets the output frequency if
Auto Output is False.
Auto Start
True
False, True
Enables or disables the auto-
start feature of the AC6000.
Once initialized, unit will
automatically return to online
mode after a power failure
unless user initiates a power
off.
Содержание AC6000