background image

13281-9-0709

Page 11

Reassembly And Resealing Vent-Air Intake System

When vent-air intake system is removed for servicing the furnace, 

the following steps will assure proper reassembly and resealing of 

the vent-air intake assembly.

1.  Remove old caulking beneath the collar of the outside mounting 

plate. apply  new  caulking  beneath  the  collar  of  the  outside 

mounting plate. Use additional caulking to correct uneven wall 

surface, such as clapboard.

2.  Insert six inch air tube on outside mounting plate 

INTO

 six 

inch air tube attached to air drop. Position the outside mounting 

plate so that six inch air tube has a slight downward slope to 

the outside. 

The downward slope is necessary to prevent the 

entry of rainwater.

 attach outside mounting plate to exterior 

wall with four (4) 10 x 1 1/2" screws.

3.  Place four inch flue tube on vent cap 

OVeR

 four inch flue tube 

attached to combustion chamber. attach vent cap to outside 

mounting plate with three (3) 10 x 1/2" screws. 

4.  Reassembly  and  resealing  vent-air  intake  system  is 

completed.

Installing a Vent Near a Window Ledge, 

Other Type of Projection or on Siding (vinyl, aluminum, etc.)

Direct  vent  furnaces  are  designed  to  be  installed  on  a  uniform 

outside wall. When the wind comes from any angle (up, down or 

from either side), it must hit the vent cap equally over both the air 

inlet and the flue outlet portions of the vent. Any wall projection, 

such as a door or window casing, which disturbs the wind on one 

side of the air inlet section will result in back pressure on the flue 

section smothering the flame and eventual pilot outage.

When the vent cap is to be installed on siding or it appears that 

a projection within 6" of any side of the air inlet section could 

shield the air inlet section, the entire vent should be supported 

away from the wall at least the distance of the projection. 2" x 4" 

framing whose outside dimensions match the overall dimensions of 

the mounting plate is recommended. The 2" x 4" framing protects 

siding from possible warpage or discoloration. all joints can then 

be sealed and painted. The wall depth plus the additional depth 

of the 2" x 4" framing should not exceed a total depth of 19" for 

DV-55.  (See Figure 10)

Vinyl siding vent kit, DV-822, is available from empire Comfort 

Systems, Inc. The depth is 3", which enables the vent cap to be 

extended away from siding or projections. The wall depth plus the 

additional 3" depth of the vinyl siding vent cap extension should 

not exceed a total depth of 19" for DV-55.  (See Figure 10)

Warning: When vinyl siding vent kit, DV-822 or 2" x 4" 

framing  is  added  to  an  existing  installation  (furnace  is 

installed) do not attempt to add sections of pipe to the flue 

outlet tube or air inlet tube. An air tight seal is required for 

both tubes. Refer to Parts List, page 19 to order tubes.

Figure 10 

Figure 11

INSTALLATION INSTRUCTIONS (continued)

Содержание DV-55IPT-1

Страница 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Страница 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Страница 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Страница 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Страница 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Страница 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Страница 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Страница 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Страница 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Страница 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Страница 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Страница 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Страница 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Страница 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Страница 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Страница 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Страница 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Страница 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Страница 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Страница 20: ...13281 9 0709 Page 20 PARTS VIEW...

Страница 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Страница 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Страница 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Страница 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: