background image

13281-9-0709

Page 8

Figure 3

Checking Manifold Pressure

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 3.5" w.c. at the valve outlet with the 

inlet pressure to the valve from a minimum of 5.0" w.c. for the 

purpose of input adjustment to a maximum of 7.0" w.c.  Propane 

gas  models  will  have  a  manifold  pressure  approximately  10.0" 

w.c. at the valve outlet with the inlet pressure to the valve from a 

minimum of 11.0" w.c. for the purpose of input adjustment to a 

maximum of 13.0" w.c. 
a 1/8" N.P.T. plugged tapping, accessible for test gauge connection, 

is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure 

and full on in 10 seconds.

Safety Lockout

S8600H  module  provides  100  percent  shutoff,  or  safety 

lockout.  If the pilot fails to light within 90 seconds, the 

control system will shut down.  The control system must 

be reset by setting the thermostat below room temperature 

for one minute or by turning off power to the module for 

one minute.

Clearances

  1.  In selecting a location for installation, it is necessary to provide 

adequate  accessibility  clearances  for  servicing  and  proper 

installation.

  2. 

The DV4T-59-1, 5" to 9" wall depth is the standard vent 

kit provided with the DV-55IPT. See Accessories Page 6 to 

order vent kits for wall depths of 8" to 12" or 12" to 19". 

The use of tubes not supplied by the manufacturer results 

in unsatisfactory performance.  

  3.  The DV-55IPT can be attached to the wall or recessed into the 

wall up to 4 inches in depth but the minimum 5 inches vent/air 

intake system wall depth must be maintained.  example:  If 

furnace is recessed into the wall at a depth of 4 inches, the 

minimum wall depth must be 5 inches behind the furnace.

  4.  The wall in which the furnace is recessed has (0) zero clearance 

to the furnace sides and top. 

  5.  When using side discharge registers, SOR-1 or SOK-1, the 

furnace cannot be recessed into the wall. 

  6.  Clearance to sidewall or combustible material is 4 inches.

  7.  Ceiling clearance is 4 inches.

  8.  Floor and rear wall clearance is (0) zero inches.

  9.  Clearance of 18 inches is required to sidewall or combustible 

material when flush mounted SOR-1, side outlet register is 

used. See Figure 4.

 10.  The minimum distance from the center of the vent cap to the 

nearest outside corner or obstruction is 24 inches. 

The vent terminal of a direct vent appliance with an input over 

50,000 BTU per hour shall be located at least 12 inches from any 

opening through which flue gases could enter a building.  The 

bottom of the vent terminal and the air intake shall be located at 

least 12 inches above grade.  

WARNING:   The  nearest  point  of  the  vent  cap  should 

be a minimum horizontal distant of six (6) feet from any 

pressure regulator. In case of regulator malfunction, the 

six (6) feet distance will reduce the chance of gas entering 

the vent cap.

Figure 4

CLEARANCES

Содержание DV-55IPT-1

Страница 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Страница 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Страница 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Страница 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Страница 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Страница 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Страница 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Страница 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Страница 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Страница 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Страница 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Страница 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Страница 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Страница 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Страница 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Страница 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Страница 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Страница 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Страница 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Страница 20: ...13281 9 0709 Page 20 PARTS VIEW...

Страница 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Страница 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Страница 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Страница 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: