background image

13281-9-0709

Page 18

S8600HTROUBLESHOOTING GUIDE

Note: Before troubleshooting, familarize yourself with the startup

and checkout procedure.

Check line voltage power low voltage transformer, limit

,

control, thermostat and wiring.

Pull ignition lead
and check spark at
ignition stud.
Spark okay?

Replace module.

No

• Check that all manual gas valves are open. Supply tubing

and pressures are good, and pilot burner orifice is not blocked.

• Check electrical connections between module and pilot

operator on gas control.

• Check for 24VAC across PV— MV/PV terminals on module.

If voltage is okay

, replace gas control. If not, replace module.

•Note: If S8600H goes into lockout, reset system.
• Check continuity of ignition cable and ground wire.
• Check that pilot flame covers electrode.
• Adjust pilot flame current. Minimum signal should read 1.0

microamp.

• If problem persists, replace module.

• Check ignition cable, ground wiring, ceramic insulator

and gap, and correct.

• Check boot of the ignition cable for signs of melting or

buckling. Take protective action to shield cable and boot
from excessive temperatures.

• Check for 24VAC across MV

-MV/PV terminals. If no voltage,

replace module.

• Check electrical connections between module and gas control.

If okay, replace gas control.

Note: If S8600H goes into lockout, reset system.
• Check continuity of ignition cable and ground wire. Note: If

ground is poor or erratic, shutdowns may occur occasionally
even though operation is normal at the time of checkout.

• If checks are okay

, replace module.

• Check for proper thermostat operation.
• Remove MVlead at module: If valve closes, recheck

thermostat and wiring. If not, replace gas control.

No

No

No

No

No

No

No

Repeat procedure until troublefree operation is obtained.

Yes

Yes

Yes

Yes

Yes

Yes

Yes

START

Turn gas supply off

.

Turn thermostat
to call for heat.

Spark stops when
pilot is lit?

Power to module.
(24 VAC nominal)

Spark across
Igniter/sensor gap.

Turn gas supply on.
Pilot burner lights?

Main burner lights?

System runs until
call for heat ends?

Call for heat ends.
System shuts of

f?

Troubleshooting ends.

Yes

Содержание DV-55IPT-1

Страница 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Страница 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Страница 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Страница 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Страница 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Страница 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Страница 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Страница 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Страница 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Страница 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Страница 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Страница 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Страница 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Страница 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Страница 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Страница 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Страница 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Страница 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Страница 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Страница 20: ...13281 9 0709 Page 20 PARTS VIEW...

Страница 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Страница 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Страница 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Страница 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: