background image

13281-9-0709

Page 17

Important

  1.  The following service procedures are provided as a general 

guide.  

  2.  Meter readings between gas control and ignition module must 

be taken within the trial for ignition period.  Once the igni-

tion module locks out, the system must be reset by setting the 

thermostat down for at least one minute before continuing.

  3.  If any component does not function properly,  make sure it is 

correctly installed and wired before replacing it.

  4.  The ignition module cannot be repaired.  If it malfunctions, it 

must be replaced.

  5.  Only trained, experienced service technicians should service 

intermittent pilot systems. 

Perform the 

ChECKoUt

 steps on page 15 as the first step in 

troubleshooting.  Then check 

TROUBLESHOOTING GUIDE

  

to pinpoint the cause of the problem.  If troubleshooting indicates 

an ignition problem, see 

Ignition System Checks 

below to isolate 

and correct the problem.
Following troubleshooting, perform the 

ChECKoUt

 procedure 

(page 15) again to be sure system is operating normally.

Ignition System Checks

Step 1:  Check ignition cable.

Make sure:

  a.  Ignition cable does not touch any metal surfaces.

  B.  Ignition cable is no more than 36 inches long.

  C.  Connections to the ignition module and to the  igniter-sensor 

are clean and tight.

  D.  Ignition cable provides good electrical continuity.
Step 2:   Check ignition system grounding.

 

Nuisance shutdowns are often caused by a poor or erratic 

ground.

  a.  a common ground, usually supplied by the pilot burner bracket, 

is required for the module and the pilot burner/igniter sen-

sor.

•  Check for good metal-to-metal contact between the pilot 

burner bracket and the main burner.

•  Check the ground lead from GND (BURNER) terminal on 

the module to the pilot burner.  Make sure connections are 

clean and tight.  If the wire is damaged or deteriorated, replace 

it with No.  14-18  gauge, moisture-resistant, thermoplastic 

insulated wire with 105 C (221 F) minimum rating.

•  If flame rod or bracket are bent out of position, restore to 

correct position.

•  Replace  pilot  burner/igniter  sensor  if  insulator  is 

cracked.

Step 3:  Check spark ignition circuit.  

You will need a short jumper 

wire made from ignition cable or other heavily insulated 

wire.

  a.  Close the manual gas valve.

  B.  Disconnect the ignition cable at the SPaRK terminal on the 

module.

WARNING

When performing the following steps, do not touch stripped 

end of jumper or SPARK terminal.  the ignition circuit 

generates 13,000 volts at 25 pf load and electrical shock 

can result.

C. energize the module and immediately touch one end of the jumper 

firmly to the GND terminal on the module.  Move the free end 

of the jumper slowly toward the SPaRK terminal until a spark 

is established.

  D.  Pull the jumper slowly away from the terminal and note the 

length of the gap when sparking stops.  Check table below.

Step 4:  Check pilot flame current.

  a.  Turn off furnace at thermostat.

  B.  Disconnect main valve wire from the TH or MV terminal on 

the gas control.

  C.  Disconnect ground wire from GND (BURNER) terminal at 

module.

  D.  Connect a meter (dc microamp scale) in series with the ground 

lead.  

•  Disconnect  ground  lead  from  GND  terminal  on  ignition 

module.

•  Connect  the  black  (negative)  meter  lead  to  the  ignition 

module GND (BURNER) terminal.

•  Connect the red (positive) meter lead to the free end of the 

ground lead.

  e.  Set thermostat to call for heat.  The spark will light the pilot but 

the main burner will not light because the main valve actuator 

is disconnected.

  F.  Read the meter.  The flame sensor current must be steady and 

at least 1.0 ua.

  G.  If the reading is less than the minimum or unsteady,

•  Make sure pilot flame envelopes 3/8 to 1/2 inch of the flame 

rod.  

•  If necessary, adjust pilot flame by turning the pilot adjustment 

screw on the gas control clockwise to decrease or counter-

clockwise to increase pilot flame.  Following adjustment, 

always  replace  pilot  adjustment  cover  screw  and  tighten 

firmly to assure proper gas control operation.

•  Check for cracked ceramic insulator, which can cause short 

to ground, and replace igniter-sensor if necessary.

•  Make sure electrical connections are clean and tight.  Replace 

damaged wire with moisture-resistant No. 18 wire rated for 

continuous duty up to 105 C (221 F).

  H.  Remove  meter  and  reconnect  all  wires.    Return  system  to 

normal operation before leaving job.

ARC LENGTH

ACTION

No arc or arc less than 1/8 

inch.

arc 1/8 inch or longer.

Check external fuse, if pro-

vided.

Verify power at module input 

terminal.

Replace module if fuse and 

power okay.

Voltage output is okay.

TROUBLESHOOTING

Содержание DV-55IPT-1

Страница 1: ...ath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vici...

Страница 2: ...6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Mainte...

Страница 3: ...arandfreefromcombustible material gasoline and other flammable vapors and liquids Do examine venting system periodically and replace damaged parts Do make a periodic visual check of pilot and burners...

Страница 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorptio...

Страница 5: ...torasrequiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to t...

Страница 6: ...alled so that all burners and burner ignition devices are located not less than 18 above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehi...

Страница 7: ...ame to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will...

Страница 8: ...t kits for wall depths of 8 to 12 or 12 to 19 The use of tubes not supplied by the manufacturer results in unsatisfactory performance 3 The DV 55IPT can be attached to the wall or recessed into the wa...

Страница 9: ...ide outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall...

Страница 10: ...ntrol compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1...

Страница 11: ...nlet and the flue outlet portions of the vent Any wall projection such as a door or window casing which disturbs the wind on one side of the air inlet section will result in back pressure on the flue...

Страница 12: ...ice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lo...

Страница 13: ...ilot flame and the spark gap are factory checked and tested After use cleaning may be required for the proper flame The correct flame will be a short blue inner flame with a much larger light blue out...

Страница 14: ...sed plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can be plugged into the adapter and be e...

Страница 15: ...switch type 24 Vac thermostats capable of supplying rated voltage and current to the module AMBIENT TEMPERATURE RATING Minus 40 F to plus 175 F minus 40 C to plus 79 C RELATIVE HUMIDITY RATING 5 to 9...

Страница 16: ...ALVE PILOT OPERATOR OPENS PILOT BURNER OPERATION PILOT BURNER LIGHTS MODULE SENSES FLAME CURRENT PILOT BURNER DOES NOT LIGHT OR MODULE RESPONSE S8600H AFTER90SECONDS PILOTVALVE CLOSES SPARKSTOPS LOCKO...

Страница 17: ...ion cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module Warning Whenperformingthefollowingsteps donottouchstripped en...

Страница 18: ...orrect Check boot of the ignition cable for signs of melting or buckling Take protective action to shield cable and boot from excessive temperatures Check for 24 VAC across MV MV PV terminals If no vo...

Страница 19: ...NEL LOWER 29 DV 826 REAR BURNER ASSEMBLY 30 R 1617 SPARK PLUG WIRE 31 R 714 L PILOT WITH ORIFICE LPG GAS 31 R 714 N PILOT WITH ORIFICE NAT GAS 32 DV 808 PILOT TUBING 33 DV 824 FRONT BURNER ASSEMBLY 34...

Страница 20: ...13281 9 0709 Page 20 PARTS VIEW...

Страница 21: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Страница 22: ...13281 9 0709 Page 22 SERVICE NOTES...

Страница 23: ...13281 9 0709 Page 23 SERVICE NOTES...

Страница 24: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: