31455-4-1113
Page 35
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS
Figure 60
Figure 61
7. Remove outside mounting plate with tube attached from wall.
Mark and cut the extra length of the 6 5/8” (168mm) diameter
tube from the opposite end. Do not crimp or enlarge tube.
8. Attach the 4” (102mm) diameter flue outlet tube onto the rigid
venting system or directly to fireplace. Ensure the 4” (102mm)
diameter flue outlet tube is placed as far as possible onto the
rigid venting system. Mark the 4” (102mm) diameter flue outlet
tube 2 1/2” (64mm) beyond the vinyl siding kit or wall. S
ee
Figure 61.
Remove the 4” (102mm) diameter flue outlet tube
from rigid venting system. When installing directly to fireplace,
tape gasket needs to be used.
9. Mark or wrap tape completely around the tubes at the marked
points to help in making a true cut. Do not crimp or enlarge
tubes.
10. From outside: Push the 6 5/8” (168mm) diameter inlet tube/
mounting plate onto end of rigid venting system to correct
position. Fasten the outside mounting plate to the vinyl siding
kit or wall with four 10 x 1 1/2” screws. (Ensure upward slope).
11. From inside: Attach the inlet tube to the collar on the back of the
fireplace (or the rigid venting system) using three self tapping
screws.
12. Seal the 4” (102mm) diameter flue outlet tube. Follow instruc
-
tions and diagram.
See Figure 62.
13. Fasten 4” (102mm) diameter flue outlet tube in place. Do not
“twist” the flue outlet tube into the fireplace collar (or rigid vent
-
ing system). Hold the tube by the seam and push in using a
perpendicular “rocking” motion. This ensures the seam on the
tube stay intact.
14. Fasten vent cap end using three 10 x 1/2” screws to mounting
plate.
Sealing 4” (102mm) Diameter Flue Outlet Tube
Figure 62
NOTICE
:
Tape gasket to be applied prior to installing to fireplace
flue outlet tube only. Tape gasket should not be used when mating
the flue outlet tube to a rigid venting system.
Содержание DVP42 Series
Страница 20: ...31455 4 1113 Page 20 Figure 29 Figure 30 Figure 31 EXAMPLES TOP VENT RUN...
Страница 42: ...31455 4 1113 Page 42 Figure 75 MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM...
Страница 54: ...31455 4 1113 Page 54 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING...
Страница 64: ...31455 4 1113 Page 64 PARTS VIEW...